Section 5 – Data Field Descriptions
5-9
Conditions That Affect Cross-Zone Operation
In the event of a continuous fault (lasting at least 5 minutes) on one of the paired zones, a fault on the second zone
causes an alarm immediately.
If one of the zones in a pair is bypassed or has a zone response type set to 0, the cross-zoning feature does not apply.
If an entry/exit zone is paired with an interior follower zone, be sure to enter the entry/exit zone as the first zone of the
pair. This ensures that the entry delay time is started before the follower zone is processed.
If a relay is programmed to activate on a fault of one of the zones, the relay activates without the other zone being faulted.
If a relay is programmed to activate on an alarm or trouble, both zones must trip before the relay activates, and both
zones must restore for the relay to deactivate (if relay is programmed to deactivate on a Zone List Restore).
If the one of the zones trips and the second zone does not trip within the 5-minute period, an error message is
reported to the central station. The Contact ID event code is 378.
FIELD TITLE and DATA ENTRIES EXPLANATION
1*22
Cross Zoning Pair One
Enter 001-250
Enter 000,000 to disable
Select the first pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be set to 000,000 for Commercial Fire and Burglary installations.
1*23
Cross Zoning Pair Two
Enter 001-250
Enter 000,000 to disable
Select the second pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be set to 000,000 for Commercial Fire and Burglary installations.
1*24
Cross Zoning Pair Three
Enter 001-250
Enter 000,000 to disable
Select the third pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be set to 000,000 for Commercial Fire and Burglary installations.
1*25
Cross Zoning Pair Four
Enter 001-250
Enter 000,000 to disable
Select the fourth pair of cross zones, which must both be faulted within a 5-
minute period to cause an alarm.
Must be set to 000,000 for Commercial Fire and Burglary installations.
1*26
Panic Button or Speedkey
For A, B, C keys:
00 = panic function
01-32 = macro number
For D key:
00 = to select a macro to execute when key
is pressed
01-32 = macro number
Select for the A, B, and C keys whether the system performs a panic or a
speedkey function when the key is pressed.
Select for the D key whether the system performs a specific macro or if the
user will select a macro when the key is pressed.
1*28
RF Transmitter Low Battery
Sound
0 = disarmed state only
1 = both armed and disarmed states
Select when the RF transmitter low-battery condition should display and
audible beep annunciate on the keypad.
Must be 1 for Commercial Fire and UL Commercial Burglary installations.
1*29
RF Transmitter Low Battery
Reporting
0 = disable
1 = enable
If enabled, the system sends a Trouble message for RF transmitter low-
battery condition to the central station.
NOTE: The Trouble message will be sent for a transmitter supervision failure,
independent of this selection.
Must be 1 for Commercial Fire and UL Commercial Burglary installations.
1*30
RF Receiver Supervision Check-
in Interval
Enter 02-15 times 2 hours (4-30 hours).
00 = disable receiver supervision.
Select the check-in monitoring interval for the RF receiver(s).
Failure of a receiver to receive any RF signal within the time entered results in
the activation of the response type programmed for zone 990 for the first
receiver and zone 988 for the second receiver and their related
communication reports.
Maximum is 2 (4 hr) for Commercial Fire and UL Commercial Burglary
installations.
1*31
RF Transmitter Check-in Interval
Enter 02-15 times 2 hours (4-30 hours).
00 = disable transmitter supervision.
Select the check-in monitoring interval for the RF transmitters.
Failure of an individual transmitter to send a supervision signal within the time
entered will result in a trouble response and related communication report.
Maximum is 2 (4 hr) for Commercial Fire and UL Commercial Burglary
installations.