VISTA-128FBP/VISTA-250FBP Installation and Setup Guide
5-6
FIELD TITLE and DATA ENTRIES EXPLANATION
*54
Unattended Mode
0 = disable
1 = enable
If enabled, the installer may initiate an unattended download session by
entering Code #89.
NOTES:
Must be set to 0 for UL installations (downloading is not UL Listed).
The following fields must be programmed first: primary subscriber account
number field *32; primary phone number field *33; downloader phone
number field *35. Or you can go into the Unattended Program Mode, from
normal operating mode, by entering Installer Code + [#] + [8] + [9].
*56
Dynamic Signaling Delay
Enter 00-15 times 15 seconds.
Select the time the panel should wait for acknowledgment from the first
reporting destination before it attempts to send a message to the second
destination (first and second destinations are determined in field
57).
NOTES: A minimum of 45 seconds is recommended when the Communicator
is set to be the primary report path. If the delay is short (30 seconds or less),
the communications device does not have enough time to sent the
acknowledgement back to the panel, therefore the report would be sent out
via the dialer.
If the acknowledgment is received before the delay time expires, no message
is sent to the second destination.
*57
Dynamic Signaling Priority
0 = Primary Dialer
1 = Communicator
Select the initial reporting path for central station messages.
*58
Communicator Central Station #1
Category Enable
0 = disable
1 = enable
This field has six entries as follows: Alarm, Trouble, Bypass, Open/Close,
System, and Test. If enabled, the reports are sent to the primary subscriber ID
of the Communicator.
*59
Communicator Central Station #2
Category Enable
0 = disable
1 = enable
This field has six entries as follows: Alarm, Trouble, Bypass, Open/Close,
System, and Test. If enabled, the reports are sent to the secondary subscriber
ID of the Communicator.
*77
Auto Trouble Restore
0 = disable
1 = enable
If enabled, each trouble and supervisory condition automatically clears the
keypad display and stops the keypad beeping when the zone returns to a
ready/normal state. This applies to ALL trouble and supervisory types. The
system also sends the Trouble/Supervisory Restore report to the central
station, if programmed.
If a partition has more than one trouble/supervisory condition present at the
same time, the system automatically clears the keypad display of each zone
as it restores, but the keypad continues to beep until all the zones restore.
NOTE: If this option is set to 0 (disable) then the operation is that restore
reports will be sent to the CS when the actual restoral on the zone occurs,
however the keypad display will remain showing the condition until a valid
code is entered.
Must be 1 for Commercial Fire installations.
*79
Zone Type Restores for Zone
Types 1-8
0 = disable
1 = enable
This field has eight entries, one for each zone type. Select the zone types that
will send Restore reports.
*80
Zone Type Restores for Zone
Types 9, 10 & 14
0 = disable
1 = enable
This field has three entries, one for each zone type. Select the zone types that
will send Restore reports.
Restores must be set to 1 for Commercial Fire installations.