xiii
Program feature or option
Permitted in
UL864? Y/N
Possible settings
Settings permitted in UL 864
3✱
60 BELL 2 & AUX
RELAY TIMEOUT
Y
Enter 01-15 multiplied by 2
minutes.
00 = no timeout.
Must be set to “3” (Minimum
of 6 minutes).
3✱
82 ENABLE
BURGLARY FEATURES
ON PARTITION 1
N
0 = disable
1 = enable
Must be set to “0” (disable).
RESTRICTION FOR FIRE
RELAYS
Y
Yes
No
Restriction for # 70 must be
set to Yes when
programming fire relays.