APPENDIX C
Specifications
••••••••••••••••••••••••••••••••••••••••••••••••••
VISTA-128FBP/VISTA-250FBP CONTROL
Physical: 18"H X 14-1/2"W X 4.3"D
Electrical:
Primary Power: From ADEMCO No. 1451 Transformer with enclosure; rated 18VAC, 72VA.
Backup Battery: 12VDC, 12AH min to 34.4AH max. lead acid battery (gel type).
Alarm Power: 12VDC, 1.7A max. for each Notification Appliance Circuit.
Aux. Standby Pwr 12VDC, 1A max.
Total Power Combined auxiliary standby and alarm currents must not exceed 2.3A.
Standby Time: 24 hours with 1A aux standby load using 34.4AH battery.
Fusing: Battery input, auxiliary and Notification Appliance Circuits are protected using PTC
circuit protectors. All outputs are power limited.
Main Dialer
Line Seize: Double Pole
Ringer Equivalence: 0.7B
FCC Registration No.: AC3-USA-68192-AL-E
TLM Threshold Good line when tip-to-ring voltage greater than approximately 25V (13 when blue
jumper cut) or when handset current greater than approximately 10mA. Bad line
when both voltage and current below these levels.
Formats: ADEMCO High Speed, ADEMCO 4 + 2 Express, ADEMCO Low Speed, ADEMCO
Contact ID, Sescoa and Radionics Low Speed
Compatible Receivers
7810iR-ent
MX8000
5140DLM BACKUP DIALER MODULE
Physical: 2.75”H X 4”W X 1”D
Mounts on VISTA-128FBP main PC board shield using standoffs supplied.
Connects to VISTA-128FBP main PC board J3 header using ribbon cable supplied.
FCC Registration: AC3-USA-62628-MO-N