Section 5 – Data Field Descriptions
5-15
FIELD TITLE and DATA ENTRIES EXPLANATION
3*19
Auxiliary Input Alternate
Function Enable
0 = disable
1 = enable
If enabled, pins 5 and 9 on the J2 connector function as RS232 output and
input, respectively. If disabled, they function as fire alarm trigger and
communications device Xmit Okay. See the chart at field 3*20 for the J2
trigger configurations.
NOTE: If field 3*19 is enabled, you cannot use a communications device
connected to the J2 trigger.
3*20
Trigger Outputs Function
Selection
0 = remote keypad sounder
1 = keyswitch LEDs
Select the function of the J2 trigger outputs. See chart below.
J2 Pin
Field 3*19 = 0
Field3*20 = 0
Field 3*19 = 0
Field3*20 = 1
Field 3*19 = 1
1 Panic Alarm Panic Alarm As selected in field 3*20
2 Trouble Trouble As selected in field 3*20
3 Burglary Alarm Burglary Alarm As selected in field 3*20
4 Fire Supervisory Fire Supervisory As selected in field 3*20
5 Fire Alarm Fire Alarm RS232 Output
6
Remote Console
Sounder
Keyswitch Ready LED As selected in field 3*20
7 Open/Close Keyswitch Armed LED As selected in field 3*20
8 Ground Ground Ground
9 Communicator Xmit Okay Communicator Xmit Okay RS232 Input
3*21
Maximum Number of Dialer
Attempts
Enter the number of dialing attempts 1-8.
Select the maximum number of dialer attempts for the system.
NOTE: Must be 3, 4, or 5 for NFPA 72 compliant systems if a secondary
phone number is programmed.
3*30
Dialer Selection
0 = disable
1 = enable
This field has two entries, one for each dialer (main and backup). Enter 1 if the
dialer is being used.
NOTE: If 3*30 is disabled (0, 0), the panel does not report at all via
communications device.
3*31
Backup Dialer TouchTone or
Rotary
0 = rotary
1 = touchtone
Select the dialing method for the backup dialer.
3*50
Zone Type Restore Enables for
Types 16-18
0 = disable
1 = enable
This field has three entries, one for each zone type. Select the zone types that
will send Restore reports.
Must be 1 for UL commercial fire and burglary installations
3*55
Reset on Second OFF for Bell 1
0 = disable
1 = enable
If enabled, the system silences bell 1 output when the second User Code +
OFF Code is entered after a fire alarm. If disabled, the system silences bell 1
output after the first User Code + OFF.
3*56
Reset on Second OFF for Bell 2
0 = disable
1 = enable
If enabled, the system silences bell 2 output when the second User Code +
OFF Code is entered after a fire alarm. If disabled, the system silences bell 2
output after the first User Code + OFF.
3*57
Confirmation of Arming Ding Bell
2 & Auxiliary Relay
0 = disable
1 = enable
This field has two entries, one for bell 2 and one for the auxiliary relay. If
enabled, produces ½-second external alarm sounding (ding) at the end of
exit delay (or after kissoff from the central station, if sending closing reports).
NOTE: If using a keyfob, when the button is pressed, either for arming or
disarming, the bell will ding indicating that the button is working.
Must be 1 for Commercial Burglary installations.