– 70 –
Relay Programming Menus
From #93 Menu Mode, select Relay Programming Menu.
Press * to advance to next screen. Press # to backup to previous screen.
Enter Relay No.
(00=Quit) 01
Enter the relay (output device) identification number
1-16. This is a reference number only, for
identification purposes. The actual module address
and relay number on the module is programmed in
the last two prompts.
02 A EV ZL ZT P
STT 0 0 0 00
The console will display a summary START screen.
02 A EV ZL ZT P
STOP 0 0 0 00
The console displays a summary STOP screen.
02 Relay Action
No Response
Enter the desired relay action as follows:
0=not used; 1=closed for 2 secs.; 2=stay closed;
3=pulse on/off
02 Start Event
Not used
Enter the event code to start the relay action as
follows: 0=not used; 1=alarm; 2=fault; 3=trouble;
4=restore
02 Start: Zn LIST
No list
If a zone list is being used to start this relay action,
enter the zone list number 1-8. If a zone list is not
being used, enter 0.
02 Start: Zn Typ
If a zone type/system operation is being used to start
the relay action, enter the 2-digit code as listed in the
Zone Type/System Operation definitions section
earlier.
02 Start Part
Enter 0 for any partition. Enter 1-8 for specific
partition number.
02 Stop: Zn LIST
No list
If a zone list is being used to stop this relay action,
enter the zone list number 1-8. If a zone list is not
being used, enter 0.
02 Stop: Zn Typ
If a zone type/system operation is being used to stop
the relay action, enter the 2-digit code as listed in the
Zone Type/System Operation definitions section.
02 Stop Part
Enter 0 for any partition. Enter 1-8 for specific
partition number.
Relay Group
Relays may be grouped for common activation by
time driven events (commands 06-10). Enter 0 (no
group) or 1-8 for specific partition number.
Restriction
1=yes 0=no
The system may have some devices which are not
intended to be under end user control, such as
relays activating fire doors or machinery. Enter 1 if
the end user will be restricted from accessing this
relay group.
Relay Type
Enter 1 for relays. Enter 2 for X-10 devices.
House Code
For X-10 devices, enter the letter house code. A=0,
B=1, C=2, etc. (00-15)
Unit code
For X-10 devices, enter the numerical unit code (01-15)
ECP ADDRESS
For relay module (4204) outputs, enter the actual
relay module's address set by its DIP switch (01-15).
Up to 4 modules can be installed in a system.
MODULE RELAY #
For relay module (4204) outputs, enter the specific
relay number on that module (1-4).
The console displays the two summary screens again.