NOTES:
1. 685 Receiver software must be rev. 4.6 or higher. Earlier versions will not
hold the phone line connection.
2. Contact ID code for "listen-in to follow" audio alarm verification is "606."
Contact ID is the only reporting format that will send a "listen-in-to-follow."
Audio Alarm
Verification Module
Connections
Connect the Audio Alarm Verification module's falling edge trigger input (terminal
5 on Eagle model 1241) to J7 connector trigger output, or to a 4204 relay
module, as shown in the various diagrams at the end of this section.
Programming Audio
Alarm Verification
Module Options
1. Enter data field programming mode: [Installer Code] + 8 + 0 + 0.
Program the following data fields:
1*46 AUXILIARY OUTPUT ENABLE: Set for 3 (unless using 4204 relay
module).
1*60 ALARM VERIFICATION: Set for 1.
1*66 SILENCE BELLS DURING AAV: Set for 1.
*81 CANCEL REPORT: Set for non-zero digit.
*45 PRIMARY DIALER FORMAT: Set for 1 (Contact ID).
If you need more information about actual programming procedures, refer to the
PROGRAMMING GUIDE.
2. Zone 5 must be programmed for response type 10 and the EOLR must
be removed. Zone 5 is no longer available as a protection zone.
3. If using a 4204 relay instead of the J7 trigger, program the relay to trip on
Zone Type/Sys. Op. 60--Audio Alarm Verification.
4. Press *99 to exit program mode.
5. Enter [Installer Code] + OFF to cancel the system's settling delay.