
– 9 –
*33 PRIMARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2-second pause
*34
SECONDARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2-second pause
*35
DOWNLOAD PHONE NO.
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2-second pause
*36
DOWNLOAD ID NO.
| | | | | | | |
Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]
*37
DOWNLOAD COMMAND ENABLES
Dlr Shtdwn
Sys Shtdwn
0
Not Used
Rmt Byp
Rmt Disarm
Rmt Arm
Upld Pgm
Dwnld Pgm
See field 1*53 for Callback disable option; [1=enable];
0=disable. For Commercial Burglary and Commercial Fire
installations, all entries must be "0."
*38 PREVENT ZONE XXX BYPASS [000] | |
001-250; 000 if all zones can be bypassed
*39 ENABLE OPEN/CLOSE REPORT FOR [1]
INSTALLER CODE 1=enable; 0=disable
*40 OPEN/CLOSE REPORT FOR KEYSWITCH [0]
1=enable; 0=disable
*41 NORMALLY CLOSED or EOLR (Zones 3-8) [0]
1=N.C.loops; 0=EOLR supervision.
Must be "0" for Commercial Burglary and Commercial Fire
installations.
*42 DIAL TONE PAUSE [0]
0=5 seconds; 1=11 seconds; 2=30 seconds.
Must be "0" Commercial Burglary and Commercial Fire
installations.
*43 DIAL TONE DETECTION [1]
1=wait for true dial tone; 0=pause, then dial
*44 RING DETECTION COUNT [00] |
01-14; 15=answering machine; 00=no detection.
Must be "00" for Commercial Burglary and Commercial Fire
installations.
*45 PRIMARY FORMAT [1]
0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed;
3= ADEMCO Express
*46 LOW SPEED FORMAT (Primary) [0]
0= ADEMCO Low Speed; 1=Sescoa/Radionics
*47 SECONDARY FORMAT [1]
0=Low Speed; 1=Contact ID; 2= ADEMCO High Speed;
3= ADEMCO Express
*48 LOW SPEED FORMAT (Sec.) [0]
0= ADEMCO Low Speed; 1=Sescoa/Radionics
*49 CHECKSUM VERIFICATION [0] [0]
1=enable; 0=disable Prim Sec
*50 SESCOA/RADIONICS SELECT [0]
1=Sescoa; 0=Radionics
*51 DUAL REPORTING [0]
1=yes; 0=no If used with Spilt Reporting "1" option (1*34),
alarms and alarm restores go to both primary and secondary
numbers, while all other reports go to secondary only. If used
with Split Reporting "2" option, alarms and alarm restores go
to both, open/close and test messages go to secondary only,
while all other reports go to primary. If used with Split
Reporting “3” option, fire alarms and fire restores signals go to
both, all other reports go to secondary only.
*52
STANDARD/EXPANDED REPORT FOR PRIMARY
[0 0 0 0 0 0]
Alarm
Rstr
Byp
Trbl
O/C
LoBat
0=standard; 1=expanded;
NOTE: Expanded overrides 4+2 format.
*53
STANDARD/EXPANDED REPORT FOR SECONDARY
[0 0 0 0 0 0]
Alarm
Rstr
Byp
Trbl
O/C
LoBat
0=standard; 1=expanded;
NOTE: Expanded overrides 4+2 format.
*54 UNATTENDED MODE [1]
0=disable, 1=enable, if automatic downloads will be allowed
Must be "0" for Commercial Fire installations.
*56 DYNAMIC SIGNALING DELAY [03] |
Select the delay time (00-15) times 15 seconds before sending
to second destination.
NOTE: When Communicator is used as a backup to the dialer,
the Dynamic Signaling Delay (*56) should be set to a minimum
of 1 minute.
*57 DYNAMIC SIGNALING PRIORITY [0]
0=Primary dialer; 1=Communicator, as first reporting
destination.
*58 COMM
CENTRAL STATION #1 CATEGORY ENABLE
[0 0 0 0 0 0]
Alarm
Trbl
Byp
O/C
Syst
Test
0=disable, 1=enable for reports for primary subs ID of
communicator.
*59 COMM
CENTRAL STATION #2 CATEGORY ENABLE
[0 0 0 0 0 0]
Alarm
Trbl
Byp
O/C
Syst
Test
0=disable, 1=enable for reports for secondary subs ID of
communicator.
Comentarios a estos manuales