ADEMCO VISTA-250FBP Guia de preparacion Pagina 4

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 72
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 3
–4–
Program feature or option
Permitted in
UL864? Y/N
Possible settings Settings permitted in UL 864
2
18 ENABLE GOTO FOR
THIS PARTITION (partition-
specific)
N 0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.
2
21 SUPERVISION PULSES
FOR COMMUNICATIONS
DEVICE
N 0 = disable
1 = enable
Not used. Must be set to “00000”
(disable).
2
22 DISPLAY FIRE ALARMS
OF OTHER PARTITIONS
N 0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.
2
23 DISPLAY BURG, PANIC
AND CO ALARMS FOR OTHER
PARTITIONS
N 0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.
2
24 DISPLAY TROUBLES OF
OTHER PARTITIONS
N 0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.
2
30 -
2
88 (PAGER
OPTIONS)
N NA Not used.
3
01 EVENTS DISPLAY LOCK
N 0 = disable
1 = enable
Must be set to “1” (enable).
3
12 ZN TYPE 18 DELAY USE
N 0 = disable
1 = enable
Must be set to “0” (disable).
3
13 FIRE SUPERVISORY
RESPONSE TO OPEN/SHORT
(APPLIES TO ZONE TYPE 18)
N 0 = Trouble on open/Supv on short
1 = Supv on open/Supv on short
Must be set to “0”.
3
14 WATERFLOW ALARM
SILENCE OPTION
N 0 = Silenced by User Code + OFF
1 = Silenced when zone restores
Must be set to “0” (Silenced by User
Code + OFF).
3
16 DELAY FOR ZONE
TYPES 17 & 18
(Waterflow/Supervisory)
N Enter 01-15 times 2 seconds
Enter 00 for no delay
Must be set to 00 (no delay).
3
18 EXTENDED DELAY FOR
ZONE TYPES 17 & 18 Multiplies
delay in 3*16 x 4)
N 0 = no extended delay
1 = multiply delay by 4
Must be set to 0 (no extended delay).
3
19 AUXILIARY INPUT
ALTERNATE FUNCTION
ENABLE
N 0 = disable
1 = enable
Must be set to 0 (disable).
3
20 TRIGGER OUTPUTS
FUNCTION SELECTION
N 0 = remote keypad sounder
1 = keyswitch LEDs
Must be set to 0 (remote keypad
sounder).
3
21 MAXIMUM NUMBER OF
DIALER ATEMPTS
Y 1-8 Must be set at 3, 4 or 5.
3
50 ZONE TYPE RESTORE
ENABLES FOR TYPES 16-18
N 0 = disable
1 = enable
Must be set to “1” (enable).
3
55 RESET ON SECOND OFF
FOR BELL 1
N 0 = disable
1 = enable
Must be set to “0” (disable).
3
56 RESET ON SECOND OFF
FOR BELL 2
N 0 = disable
1 = enable
Must be set to “0” (disable).
3
57 BELL 2 AND AX RELAY
CONFIRM ARMING DING
N 0 = disable
1 = enable
Must be set to “0, 0” (disable).
3
59 ENABLE BELL 2 &
AUXILIARY RELAY CHIME
ANNUNCIATION
N 0 = disable
1 = enable
Must be set to “0” (disable) if Bell 2
or Aux Relay is used for Fire.
3
60 BELL 2 & AUX RELAY
TIMEOUT
Y Enter 01-15 multiplied by 2 minutes.
00 = no timeout.
Must be set to “3” (Minimum of 6
minutes).
3
82 BURGLARY FEATURES
ON PARTITION 1 ENABLE
N 0 = disable
1 = enable
Must be set to “0” (disable).
RESTRICTION FOR FIRE
RELAYS
Y Yes
No
Restriction for # 70 must be set to
Yes when programming fire relays.
Vista de pagina 3