3*13 FIRE SUPERVISORY RESPONSE TO OPEN/SHORT
(Applies to Zone Type 18) [0]
0=Trouble on open/Supervisory on short
1=Supervisory on open/Supervisory on short
NOTE: Must be set to “0” for Commercial Fire Installations.
3*14 WATERFLOW SILENCE OPTION [0]
0=silence on code = off; 1=silence when waterflow restores
NOTE: Must be set to “0” for Commercial Fire Installations.
3*16
DELAY FOR ZONE TYPE 17 & 18 [00] |
Enter 00-15 times 2 seconds
Delay cannot exceed 90 seconds in UL installations.
NOTE: Must be "00" for Commercial Fire installations.
3*17 ALTERNATE FUNCTION (TAMPER) [0]
FOR ZONE 6 0=disable; 1=enable
3*18 EXTENDED DELAY FOR TYPES 17 & 18 [0]
0=disable; 1=enable
NOTE: Must be "0" for Commercial Fire installations.
3*19 AUX INPUT ALTERNATE FUNC ENABLE [0]
0=pins 5 and 9 function as per filed 3*20;
1=pins 5 and 9 function as RXD and DTR
NOTE: Must be set to “0” for Commercial Fire Installations.
3*20 TRIGGER OUTPUT SELECTION [0]
0=Communicator full connection & remote console sounder;
1=Communicator limited connection and keyswitch LEDs
2=Communicator fire only connection and 5140LED
NOTE: Must be set to “0” for Commercial Fire Installations.
3*21 MAX NUMBER OF DIALER ATTEMPTS [8]
1-8 (3, 4 or 5 for NFPA72 compliant systems when a
secondary phone number is programmed (field *34))
3*30 DIALER SELECTION [1,0]
0=disable; 1=enable Main Backup
NOTE: If 3*30 is disabled (0, 0), the panel does not report at
all via Communicator.
3*31 BACKUP DIALER TOUCHTONE/ROTARY [1]
1=TouchTone; 0=Rotary
3*50 ZONE TYPE RESTORE ENABLES
FOR ZONE TYPES 16-18
1=enable; [0=disable]
Restores must be set to “1” for Commercial Fire installs.
3*55 RESET ON SECOND OFF FOR BELL 1 [0]
0=disable; 1=enable
NOTE: Must be set to “0” for Commercial Fire Installations.
3*56 RESET ON SECOND OFF FOR BELL 2 [0]
0=disable; 1=enable
NOTE: Must be set to “0” for Commercial Fire Installations.
3*57 BELL 2 & AUX RELAY CONFIRM [0,0]
ARMING DING Bell 2 Aux
0=disable; 1=enable.
NOTE: If using a keyfob, when the button is pressed, either
for arming or disarming, the bell will ding indicating that the
button is working.
Must be “1” for Commercial Burglary installations.
3*59 ENABLE BELL 2 & AUX RELAY [0,0]
CHIME ANNUNCIATION Bell 2 Aux
0=disable; 1=enable
NOTE: Must be “0, 0” if Bell 2 or Aux. Relay is used for fire
application.
3*60 BELL 2 & AUX RELAY TIMEOUT | |
Bell 2 Aux
Enter 00-15 times 2 minutes; 00=no timeout [00,00]
Minimum 16 minutes for Commercial Burglary installations.
3*61 AUX RELAY FUNCTION [1]
0=trouble/supervisory; 1=alarm, silenced by code = off;
2=smoke detector reset; 3=battery save; 4=alarm, silenced
by code = # = 67
NOTE: See Data Field Descriptions in the Installation and
Setup Guide for specific information.
3*82 ENABLE BURG FEATURES ON PART 1 [1]
0=disable (disables AWAY, STAY, MAX, TEST, INSTANT
and CHIME); 1=enable;
NOTE: Must be "0" for Commercial Fire installations.
3*85 ENABLE FIRE & SYSTEM ZONE BYPASS [1]
0=disable; 1=only installer can bypass;
2=only installer and master can bypass.
Applies to fire zone types 9, 16, 17, and 18 and system
zones 970-977 and to partition 1 only.