1*76 CONTROL RELAY [00] |
Relay will be pulsed for 2 seconds whenever code + [0] is
pressed. Enter relay number 01-96; 00=none.
Must be "00" for Commercial Burglary and Commercial Fire
installations.
1*77 LOG FIRST MAINTENANCE SIGNAL [0]
0=No Log; 1=Log first maintenance signal from each smoke
detector.
1*78 EXTENDED HOME CONT EVENTS [0]
Not Used. Must Be Set To “0”.
0=Limited home control command set (32 commands).
1=Extended home control command set (255 commands).
1*79 HOME CONTROL EVENTS
[0 0 0 0 0 0]
Alarm
Trbl
Byp
O/C
Syst
Test
Not Used. Must Be Set To “0” In Each Entry.
1=enable; 0=disable. Select the type of events (status
reports) transmitted via the RS232 output.
3rd Page Programming Fields (press *94)
2*00
NUMBER OF PARTITIONS [1]
Enter 1-8
2*01 DAYLIGHT SAVING TIME [03, 11] | |
START/END MONTH Start End
00-12; if no daylight saving time, enter 00,00
2*02 DAYLIGHT SAVING TIME [2, 1] |
START/END WEEKEND Start | End
Enter 1-7. 1=first; 2=second; 3=third; 4=fourth; 5=last; 6=next
to last; 7=3rd from last [1,5]
2*05 AUTO-ARM DELAY [15] |
Enter the time between the end of the arming window and the
start of auto-arming warning period, in values of 1-14 times 4
minutes 00=instant; [15=no auto arm at all]. When this delay
expires, the Auto-Arm Warning Period begins.
2*06 AUTO-ARM WARNING PERIOD [15] |
This is the time during which the user is warned to exit the
premises prior to the auto-arming of the system (beeps every
15 seconds; "ALERT" displayed). Enter 01-15 minutes.
00=instant at end of arming delay.
2*07 AUTO-DISARM DELAY [15] |
This is the time between the end of the disarming window
and the start of auto-disarming. Enter 01-14 times 4 minutes;
00=instant at end of window; 15=no auto-disarm.
2*08 ENABLE FORCE ARM FOR AUTO-ARM [0]
0=disable; 1=enable
2*09 OPEN/CLOSE REPORTS BY EXCEPTION [0]
1=enable; 0=disable
If enabled, only openings and closings occurring outside the
scheduled opening/closing windows will trigger dialer reports.
Opening reports will also be suppressed during the closing
window, in order to prevent false reports when the user arms
the system and then reenters the premises to retrieve a
forgotten item.
2*10 ALLOW DISARMING ONLY DURING [0]
ARMING/DISARMING WINDOWS
0=disable; 1=enable
See system-wide field 2*11 if enabling field 2*10. This
feature adds high security to the installation.
2*11 ALLOW DISARM OUTSIDE WINDOW [0]
IF ALARM OCCURS
Used only if field 2*10 is set to "1." If this field is enabled ("1")
the system can be disarmed outside the disarm window if an
alarm has occurred. If "0," disarming can only be done during
the disarm window. If field 2*10 is set to "0" for a partition,
this field has no effect for that partition.
2*18 ENABLE GOTO FOR THIS PARTITION [0]
1=Allow log-on from other partitions; 0=disable
NOTE: Must be disabled for partition 1 in Commercial Fire
installations.
2*19 USE PARTITION DESCRIPTORS [0]
0=disable; 1=enable
2*20 ENABLE J2 TRIGGERS FOR PARTITION [1]
0=disable; 1=enable for displayed partition
2*21 ENABLE SUPERVISION PULSES FOR COMM -
Not Used. Must Be Set To “00000”.
00000]
F
B
P
S
T
Used only for supervised connection to Communicators (e.g.
7845i-ent).
Enter 0 to disable or 1 to enable the listed outputs.
F= Fire; B= Burglary/Audible Panic; P= Silent Panic/Duress;
S= Supervisory; T= Trouble.
2*22 DISPLAY FIRE ALARMS OF [0]
OTHER PARTITIONS
0=disable; 1=enable.
Must be set to “0” (disable) for partition 1.
2*23 DISPLAY BURG, PANIC and CO [0]
ALARMS OF OTHER PARTITIONS
0=disable; 1=enable.
Must be set to “0” (disable) for partition 1.
2*24 DISPLAY TROUBLES OF OTHER [0]
PARTITIONS
0=disable; 1=enable
Must be set to “0” (disable) for partition 1.
2*30 through 2*88 (PAGER OPTIONS) - Not Used.
4th Page Programming Fields (press *94)
3*00
DISPLAY TRBL INSTEAD OF CHECK [0]
0=CHECK; 1=TRBL
3*01 EVENTS DISPLAY LOCK [1]
0=scroll all alarms; 1=lock display of first fire alarm
NOTE: Must be set to “1” for Commercial Fire Installations.
3*12 ZN TYPE 18 DELAY USE [1]
0=disable; 1=enable
NOTE: Must be set to “0” for Commercial Fire Installations.