– 33 –
RF Expander
PROMPT
EXPLANATION
01 RF EXPANDER
HOUSE ID 00
If you selected device type 03 (RF receiver), this prompt appears. Enter the 2-digit House ID (00-31).
Press [✱] to accept entry.
Output Relay Module
PROMPT
EXPLANATION
01 SUPERVISED CF?
0
If you selected device type 04 (relay module), this prompt appears. Enter 1 if the unit is a 4204CF. If not,
enter 0. If you enter 1, only Relay 1 (Output A) and Relay 3 (Output B) on each module may be programmed
for functions.
NOTE: For Commercial Fire installations, only one notification appliance module may be used, and only one
notification appliance output (A or B) may be used on that module.
Press [✱] to accept entry.
Communicator
If you selected device type 6, the 6160/6160CR-2 Keypad functions similarly to the 7720P Programming Tool. See
Figure 1
for the functions of the keys on the 6160CR-2.
1
4
7
2
5
8
0
3
6
9
#
6160CR2-001-V0
Figure 1: 6160CR-2 Key Functions for Programming the Communicator
Each key has two possible functions: a normal function and a SHIFT function. To perform a normal key function, simply press
the desired key. To perform a SHIFT key function, press SHIFT key, then press desired function key.
Normal and SHIFT key Functions:
Key Normal Key Function SHIFT Key Function
BS/ESC [BS]: Press to delete entry [ESC]: Press to quit Program Mode
Also, can reset EEPROM defaults *
↓/↑ [↓]: Scroll down programming [↑]: Scroll up programming
N/Y [N]: Press for "NO" answer [Y]: Press SHIFT-Y for "YES" answer
SHIF
T
Press before pressing a SHIFT key function. Will light READY LED. LED goes out once a key is
pressed. Press again for each SHIFT function desired.
1/A [1]: For entering the number 1 [A]: Used for entering C.S. ID number
2/B [2]: For entering the number 2 [B]: Used for entering C.S. ID number
3/C [3]: For entering the number 3 [C]: Used for entering C.S. ID number
4/D [4]: For entering the number 4 [D]: Used for entering C.S. ID number
5/E [5]: For entering the number 5 [E]: Used for entering C.S. ID number
6/F [6]: For entering the number 6 [F]: Used for C.S. ID & FAST Mode
7/S [7]: For entering the number 7 [S]: Press to display diagnostic status
8/T [8]: For entering the number 8 [T]: Press to send TEST messages
9/X [9]: For entering the number 9 [X]: Press to reset the 7845i-ent
*/SPACE [*]: Not used with 7845i-ent [SPACE]: Not used with 7845i-ent
0 [0]: For entering the number 0 No SHIFT function
#/ENTER [#/ENTER]: Press to accept entries No SHIFT function
* Active only when the "REVIEW?" prompt is displayed.