SECTION 10
Creating Schedules
•••••••••••••••••••••••••••••••••••••••
About Schedules
The VISTA-20P system provides up to 32 schedules (VISTA-15P supports 8), which can be used to
control 11 types of system events at pre-defined times. Sixteen schedules are intended for use by the
end-user, and sixteen are reserved for the installer (VISTA-15P = 4 user schedules, 4 installer
schedules). In addition, some events are also reserved for the installer only (listed in the Enter Event
prompt paragraph below).
Start Scheduling mode by entering installer code + [#] + [6] [4] while in normal operating mode.
NOTE: The master code can only access schedules 01-16 (VISTA-15P = 01-04) and events 00-07.
The following prompts are displayed:
PROMPT VALID ENTRIES EXPLANATION
ENTER SCHED NO.
00=QUIT 00
Schedule Number
VISTA-20P
01-16 = end-user schedules
17-32 = installer-only schedules
VISTA-15P
01-04 = end-user schedules
05-08- = installer-only schedules
[
] to continue
Enter the desired schedule number.
ENTER EVENT
NOTE:
Events 07 and
10 cause the keypad to
beep every 30 seconds
when messages are
displayed. Stop the
beeps by user code +
OFF.
Enter Event
00 = clear event
01 = Relay On/Off
02 = User Access
03 = Latch Key Report to Pager
04 = Forced Stay Arming
05 = Forced Away Arming
06 = Auto Disarm
07 = Display Reminder
10 = Display custom words
††
11 = Periodic Test Report
†††
[
] to continue
Enter the desired event number for event you want to occur at a
specified time.
Events 10-11 are reserved for the installer only.
Latch key report (option 03) is sent to all pagers in the users
partition (message sent is 777-7777). User must be enabled for
paging (see User Attributes in
System Operation
section).
Forced bypass is automatically enabled regardless of setting in field
*23.
††
if selected, system displays custom words 8, 9, and 10 at defined
time. Can be used as installers reminder message to the end user.
†††
see key commands in
Testing the System
section to
quickly set periodic test reporting intervals
DEVICE NUMBER
XX
Device Number
01-18 = device number
[
] to continue
This prompt appears if event 1” (relay on/off) was selected, otherwise
it is skipped.
Enter the physical device number as programmed in
79 Menu Mode,
then press [*] to continue to the Start prompt.
Device numbers 17 and 18 designate built-in triggers 1 and 2
respectively.
GROUP NUMBER
X
Group Number
1-8 = group number
[
] to continue
This prompt appears if event 2” (user access) was selected.
Otherwise it is skipped.
Press [*] to continue to the Start prompt.
PARTITION
X
Partition
0 = all partitions
1 = partition 1
2 = partition 2
3 = common
[
] to continue
This prompt appears if events 3-7,10,12 were selected. Otherwise it
is skipped.
Press [*] to continue to the Start prompt.
10-1