
Powerline Carrier Devices
1. Install the powerline carrier devices according to the
instructions included with each.
VISTA-20P: Up to 16 devices (if no relays are used)
VISTA-15P: Up to 8 devices (if no relays are used)
2. Use Programming Mode to enter the device house ID
in data field*27, and enter the unit code using *79
Output Device menu Mode.
See connections diagram in the AC Wiring paragraph for
connecting the 4300/1321X10 transformer.
Canada: Use the PSC04 Powerline Interface as shown:
1 2 3 4
SA4120XM-1 CABLE
X-10 PSC04
POWERLINE INTERFACE
YEL
RED
GRN
BLK
MODULAR PHONE CORD (not supplied)
1 - BLACK
2 - RED
3 - GREEN
4 - YELLOW
SYNC
DATA
COM
1345678
KEY
+12 AUX.
DATA
COM
SYNC
GND (-)
OUTPUT 17
(RED)
OUTPUT 18
(GREEN)
(ORANGE)
(YELLOW)
(BLUE)
(PURPLE)
(BLACK)
8-PIN TRIGGER CONNECTOR
Notes
•
When using Powerline Carrier devices, you must
use a 4300 or 1321X10 Transformer instead of
the 1321 Transformer.
•
The 4300/1321X10 Transformer provides AC
power to the control panel, and also supplies
signals from the control panel through the
premises AC wiring to the Powerline Carrier
devices (which are plugged into AC outlets). You
can then make devices that are plugged into
Powerline Carrier devices perform various
functions in response to commands you enter at
the security system keypads.
U
L
Powerline Carrier devices and the 4300
Transformer are not UL Listed for fire or burglary
functions and are intended for home automation.
On-Board Triggers
Connect field wiring to the desired trigger pin on the
8-pin trigger connector centrally located above the
terminal strip.
•
If using 1321X10 transformer and powerline
carrier devices, use the SA4120XM-1 cable. See
Wiring the AC Transformer
section for transformer
connections.
•
If only using the on-board triggers, you can use a
standard keypad cable as shown below.
U
L
If on-board triggers are used, the wiring between the
control unit and the UL Listed device must be run in
conduit, be no more than 3 feet apart and have no
intervening barriers or walls.
Notes
•
Trigger outputs are normally high, and go low
upon programmed condition.
•
The outputs can be programmed for inverted
operation (normally low, go high) using *79
Menu mode.
•
Program these triggers using *80/*81 Menu
modes as you would for any other relay output.
•
When using these outputs, note:
pin 1 = output number 17 (trigger 1):
15 ohms to ground when closed (output
low), open when off (output high, normal
default); can be used to reset smoke
detector power (must set “output normal
low = yes” in *79 Menu mode, and set for
zone type 54, fire zone reset, in *80 Menu
mode); or can support 12V relay module
†
that draws less than 100mA
pin 5 = output number 18 (trigger 2):
100 ohms to ground when closed (output
low); open when off (output high, normal
default); or can support 12V relay module
that draws less than 20mA
† e.g., Altronix AX-RSB
1345678
SA412OXM-1
CABLE
8-PIN TRIGGER CONNECTOR
KEY
TRIGCON-003-V0
+12 AUX.
DATA
COM
SYNC
GND (-)
OUTPUT 17
(RED)
OUTPUT 18
(GREEN)
(ORANGE)
(YELLOW)
(BLUE)
(PURPLE)
(BLACK)
1345678
STANDARD
KEYPAD
CABLE
8-PIN TRIGGER CONNECTOR
KEY
00-trigcon-005-V0
+12 AUX.
GND (-)
OUTPUT 17
OUTPUT 18
(RED)
(YELLOW)
(BLACK)
(GREEN)
Figure 12. On-Board Trigger Connector with Figure 13. On-Board Trigger Connector with
SA4120XM-1 Cable for Use With 1321X10 Transformer Standard Keypad Cable for Trigger Use Only
Mounting and Wiring the Control
2-11
Comentarios a estos manuales