FIELD TITLE and DATA ENTRIES EXPLANATION
*72
Bypass Restore Report Code
0 = no report
1-F = see description above *59
This is sent when a zone that has been bypassed is unbypassed.
UL: Required for UL commercial burglar alarm installations.
*73
AC Restore Report Code
0 = no report
1-F = see description above *59
Sent when AC power has been restored after an AC power outage.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*74
Low Bat Restore Report Code
0 = no report
1-F = see description above *59
Sent when a system low-battery condition is restored to normal.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*75
RF Xmtr Low Batt. Restore Code
0 = no report
1-F = see description above *59
Sent when a transmitters low battery condition is restored (i.e., new
battery installed).
UL installations: must be enabled if wireless devices are used.
Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
Miscellaneous System Fields
FIELD TITLE and DATA ENTRIES EXPLANATION
*76
Test Restore Report Code
0 = no report
1-F = see description above *59
This is sent when the Test mode is exited.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*77
Daylight Saving Time
Start/End Month
0 = Disabled 4 = April
1 = Jan # + 10 = Oct
2 = Feb # + 11 = Nov
3 = Mar # + 12 = Dec
Enter the start and end month for daylight savings time, if
applicable to the region.
*78
Daylight Saving Time
Start/End Weekend
0 = disabled 4 = fourth
1 = first 5 = last
2 = second 6 = next to last
3 = third 7 = third to last
Enter the start and end weekend for daylight savings time, if
applicable to the region.
*79
Output Device Mapping Menu Mode
Use this menu mode to enter output devices/powerline carrier
devices into the system. See Output Device Programming
section for procedures.
*80
Output Programming Menu Mode
Use this menu mode to define output functions for use with
output devices/powerline carrier devices. See Output
Programming section for procedures.
*81
Zone List Programming Menu Mode
Use the menu mode to define zone lists. See Zone List
Programming section.
*82
Alpha Descriptor Programming
Menu Mode
Use this menu mode to assign alpha descriptors to zones and/or
create partition descriptors (VISTA-20P).
*84
Auto-Stay Arm
0 = no
1 = partition 1 only
2 = partition 2 only
3 = both partitions
With this field enabled and system armed in AWAY mode at a
keypad (non-RF device), the system automatically reverts to
armed STAY (or INSTANT) mode if a door is not opened and
shut within the programmed exit delay time. An Opening report
followed by an Armed Stay report is sent to the Central Station.
Any RF device that arms the system AWAY overrides this
feature and the system remains armed in the AWAY mode.
*85
Cross Zone Timer
(in seconds)
0 = 15 secs 6 = 2-1/2 min #+12 = 8 min
1 = 30 secs 7 = 3 min #+13 = 10 min
2 = 45 secs 8 = 4 min #+14 = 12 min
3 = 60 secs 9 = 5 min #+15 = 15 min
4 = 90 secs #+10 = 6 min
5 = 2 min #+11 = 7 min
Sets the maximum amount of time in which two cross zones
must be tripped in an armed system to send an alarm message
to the Central Station. If only one cross zone is tripped during
this time, a trouble message (CID code 380) for that zone is sent
to the Central Station.
Assign cross zone pairs in zone list 4.
This option not for use in UL installations.
Installation Instructions
4-6