Ill. (A) SYSTEM CONFIGURATION (ZONES)
BASIC 9 HARD-WIRED ZONES
ZONE 1 ZONES 2 THROUGH 8
Thii zone has a 350 miltiind response and can be
These zones have a 35o millisecond response and
assigned to any zone type and can be sat up for
can be assigned to any zone type. They can be EOLR
EOLR supervision
or for closed-circuit supervised or closed circuit unsupervised, as
unsupervised use. Thii zone is the only zone that
required (program field “41 determines whether or
can
support 2-wire smoke detectors (up to 3 BRK
not these zones will use the 1,000 ohm EOLR: Enter
detectors) using an EOLR configuration.
[1] in fmld 41 to disable the use of EOLRS on zones
If EOLR supervision is required, connect all cloaed-
2 through 8). If programmed for use with EOLRS,
circuit sensors in series with one another to TBl -
both closed-circuit and open-circuit devices can be
2, (4130XM/5130XM use RED/YELLOW &
used with the 1,000 ohm EOLR resistor in series
WHITE/BROWN wires) with the 13,000 ohm
with the loop at the last device. If the use of EOLRS
resistor in series with the loop, at the last device
is disabled (“41=1), only closed-circuit devices
and then return the loop to TB2-4.
can be used. Note that the maximum resistance per
If no supervision is required, simply maintain a
zone is 300 ohms.
closed loop with all sensors connected in series
ZONE 9
with the
100p, beween TB1 -1 and T61.2 (or
WHfTE/BROWN & ORANGE). If the sensors used are
This zone is an unsupewised, fast response zone
open-circuit devioes, such as smoke detectors,
(5-1O milliseconds), and can be assigned to any
each one must be
in parallel to the next using the
zone type except fire. Only closed-circuit devices
EOLR configuration. The EOLR must then be placed
can be used in this zone. This zone should be used
across the last wired detector.
for fast response devices such as fast acting glass
break sensors or vibration sensors. Avoid using
mechanical magnetic or relay type contacts in this
zone. Note that the maximum resistance for this
zone is 100 ohms.
ZONE EXPANSION MODULE—
(Required for zones 10 through 64)
4171 XT-X M/4152LMB
To expand the system using a 2-wire Polling Loop
and/or wireless devices, a 4171 XT-XM dialer
board, and a 4152LMB Loop Module must be
installed as shown below. (The 4171 XT-XM is
factory installed in the 4140XM.)
Wires from the 4208 Zone Expander, RPMs, and
4280 are connected to Terminals 1 & 2 on the
4152LMB.