– 17 –
PROMPT
EXPLANATION
010 Silent ?
1 = YES 0 = NO 1
If you selected response type 1, 2, 3, 4, 5, or 10, this prompt will appear. Enter 1 to enable. The zone
follows all the selected response type’s characteristics, except in the alarm condition, the alarm output and
the keypad sounder do not sound and the keypad does not display the alarm condition.
Enter 0 to disable.
Press [✱] to continue.
010 Bypass Group
01-15 01
If you selected response type 1, 2, 3, 4, 5, or 10, this prompt will appear. Enter the bypass group for the
zone (01–15). This enables the user to bypass a group of zones by entering [User Code] + [6] (Bypass) +
[✱] + [Group No.] (01-15).
Enter 00 for None.
Press [✱] to continue.
010 ACCESS POINT
(00-31) 01
If response type 27, or 29 was selected, this prompt will be displayed. Enter the access point to be
controlled by the input type (00-31 for type 27; 01-15 for type 29).
Note: If you are using the VistaKey module, the access point must match the address that was set in the
module.
Press [✱] to continue.
010 ENTRY OR EXIT
0
If response type 27, or 29 was selected selected, this prompt will be displayed. Enter whether the access
point is an entry or exit point.
0 = entry; 1 = exit
Press [✱] to continue.
010 Panel ID#
(01-08) 01
If you selected response type 14, this prompt appears. Enter the panel ID#. This ID # must match the ID #
programmed in Device Programming.
Press [✱] to accept entry.
010 Partition
1
Enter the partition number (1–8) you are assigning this zone to.
Press [✱] to continue.
010 REPORT CODE
1st 03 2nd 12 3C
Enter the report code. The report code consists of 2 hexadecimal digits, each in turn consisting of 2
numerical digits. For example, for a report code of "3C," enter 03 for "3" and 12 for "C."
(Refer to the
System Communication
section in the
Installation and Setup Guide
for more information about
report codes and reporting formats.)
Press [✱] to continue.
010 INPUT TYPE
RF Xmitter 3
Input types 4 & 5 are
valid for certain 5800
Series transmitters only
(e.g., 5801, 5802, 5802CP
& 5803).
If using input type 02
with a door/window type
transmitter, only loop 1
may be used.
Input type 10 is
applicable only if
PassPoint ACS is
installed with the VISTA
Gateway Module.
If you selected response
type 14, 28, or 29 the
input type MUST be 00.
Enter the input device type as follows:
00 = not used
01 = hardwired
02 = RF motion (RM type)
03 = supervised RF transmitter (RF type)
04 = unsupervised RF transmitter (UR type)
05 = RF button-type transmitter (BR type)
06 = serial number polling loop device (SL type)
07 = DIP switch-type polling loop device
08 = right loop of DIP switch type device
09 = keypad input (code + #73)
10 = PassPoint ACS input
11 = VistaKey Door Status Monitor (DM)
12 = VistaKey Request to Exit (RE)
13 = VistaKey General Purpose (GP)
Right loops refer to the use of the right loop on a 4190WH Zone Expander Module and/or 4278 PIR, which
allow hardwired devices to be monitored by the polling loop.
If you are programming hardwired or DIP switch polling loop devices, the summary display appears after
completing this entry.
NOTE: Input types 11 (DM), 12 (RE), and 13 (GP) should only be used with VistaKey modules.
Press [✱] to continue.