
– 15 –
PROMPT
EXPLANATION
OUTPUT PGM?
1 = YES 0 = NO 0
For defining output relay functions.
RLY VOICE DESCR?
1 = YES 0 = NO 0
For entering voice descriptors for relays to be used with the 4285/4286 VIP Module.
CUSTOM INDEX ?
1 = YES 0 = NO 0
For creating custom word substitutes for VIP Module annunciation.
ACCESS POINT PGM
1 = YES 0 = NO 0
For defining the parameters for each of the VistaKey access points, including which group(s) have access
through an access point (door). See the
VistaKey-SK Installation and Setup Guide
for the detailed
programming instructions.
ACCESS GRP PGM
1 = YES 0 = NO 0
For defining the capabilities (privileges) for each group of users. See the
VistaKey-SK Installation and Setup
Guide
for the detailed programming instructions.
EVENT/ACTION PGM
1 = YES 0 = NO 0
For defining events and time windows for an access group. See the
VistaKey-SK Installation and Setup
Guide
for the detailed programming instructions.
SCHEDULED CHK-IN
1 = YES 0 = NO 0
For defining the schedule for the system to automatically call the downloader.
Zone Programming
If using 5800 Series transmitters, do not the install batteries until you are ready to enroll them. After enrolling
the transmitter, the battery need not be removed. This is to prevent enrolling the wrong serial number.
PROMPT
EXPLANATION
ZONE PROG?
1 = YES 0 = NO 0
Press 1 to enter ZONE PROGRAMMING mode. The following screens appear. Press [✱] to display the next
screen. Press # to display a previous screen.
SET TO CONFIRM?
1 = YES 0 = NO 0
This prompt appears once upon entering Zone Programming Mode.
If “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have been
entered later.
ENTER ZONE NO.
000 = QUIT 010
Zone 010 entered
↑
Enter the 3-digit zone number to be programmed, as follows:
Protection Zones = 001–250
Relay Zones = 601–632
ECP Device Supervisory Zones = 800–830
System Supervisory Zones = 970 (bell supervision), 988, 990 (RF receiver), 992 (duress), 997 (polling loop)
Keypad Panic Zones = 995, 996, 999
NOTE: When supervising the bell output (zone 970), only one device can be connected to the alarm output
(terminals 4 and 5) for UL and Fire installations.
Press [✱] to continue.
010 ZT P RC In L
00 1 10 00 1
This display appears, showing a summary of the zone's current programming. ZT = Zone Type, P =
Partition, RC = Report Code, In = the input type of device, and L = the device's loop number to which the
sensor is connected.
Some devices can support more than one zone by means of individual loops (for example, 5801, 5804,
5816, 5817, etc.). If the zone is not programmed, the display appears as shown here. If you are checking a
zone's programming, and it is programmed satisfactorily, press [#] to back up one step and enter another
zone number, if desired.
Press [✱] to continue.
Comentarios a estos manuales