
EXTERNAL SOUNDERS
Relay Output
The 4120XM provides a wet bell relay output which is used to power external
alarm sounders. Connections are made to terminals 3 (positive output) and 4
(negative return). See SUMMARY OF CONNECTIC)NS Diagram.
UL Installations For UL installations, the total current drawn from this output and the auxiliary
power output, combined, cannot exceed 700 mA. In addition, the sounding
device must be a UL Listed audible signal appliance rated to operate in a 10.2-
13.8 VDC voltage range, and must be mounted indoors. Example: Wheelock
Signals Inc. siren model 34T-12 (provides 85dB[A] for NFPA 74 & Standard 985).
Non-UL Installations The total current drawn from this output cannot exceed 2.8 amps. A battery must
be installed since this current is supplied by the battery. Up to two 702 sirens can
be used, wired in series. Up to two 719 sirens can be used, wired in parallel.
IMPORTANT: Going beyond the limits indicated above will overload the power
supply or may possibly trip the bell output thermal circuit breaker.
COMPATIBLE SOUNDERS
702 Outdoor Siren
719 Outdoor Siren
(Compact)
740 High Intensity
Sounder
ABB1031 Motor Bell&
Box
PA400B (beige)/PA400R
(red) Indoor Piezo
Sounder
Self-contained siren (driver built-in) and weatherproof for outdoor use. Can be
wired for either a steady or yelp sound and is rated at 120 dB @ 10 feet. This
siren can also be tamper protected, or can be mounted in a metal cabinet
(716), which can be tamper protected.
Compact, self-contained siren (driver built-in), and weatherproof for outdoor
use. Can be wired for a steady or yelp sound, and rated at 90 dB @ 10 feet. A
tamper protected 708BE cabinet is available.
Compact high intensity sounder rated at 123 dB @ 10 feet. This sounder emits
an ‘ear piercing”, high frequency sound, and can be mounted indoors (bracket
included) or outdoors (in 708BE cabinet).
AMSECO motor bell& box, rated at 81 dB @ 10 feet.
BRK indoor piezo sounder (red or beige), rated at 90 dB @ 10 feet.
UL NOTE: Use only UL Listed sounding devices for UL installations.
PHONE CONNECTIONS
Phone Line
Incoming phone line and handset wiring is connected to the main terminal block
Connections
(via a RJ31X jack) as follows (refer to Figure 4 and the SUMMARY OF
CONNECTIONS diagram):
Term. 22: Local Handset (TIP - Brown*)
Term. 23: Local Handset (RING – Gray*)
Term. 24:
Incoming Phone Line (TIP – Green*)
Term. 25: Incoming Phone Line (RING -
Red*)
* Colors of wires in RJ31X (CA38A in Canada) telephone wall jack.
Warning: To prevent the risk of shock, disconnect phone lines at the telco jack
before servicing the control.
If you wish to connect the control to phone lines that require ground start
capability, a
675 Ground Starl Module must be used. This module is triggered
by a triggered output (terminal 9) on the control. See
GROUND START
MODULE
paragraph.
PABX
Important!
If the communicator is connected to a telephone line inside a PABX,
be sure the PABX has a back-up power supply that can support the PABX for 24
hours. Many PABXS are not power backed up and connection internally to such a
PABX will result in a communication failure if power is lost.
-24-
Comentarios a estos manuales