VOLTAGE TRIGGER OUTPUTS (Connector TB2)
(For LORRAS, STUS, Remote Console Sounder, Remote Keyswitch)
TB2 provides 3 trigger outputs for operating the 4146 Keyswitch, triggering
auxiliary alarm sounding equipment (LORRAS, STUS, etc.), and for resetting
latching glass break detectors on zone 6.
The pin assignments for TB2 connector are shown below Use only the
SA4120XMP-2 trigger cable or the SA4120XM-2 trigger cable, as shown on
the following page.
“ Outputs 1 and 2 are open collector outputs with a series resistance of 220
ohms.
G Output 3 is an open collector output with no series resistance. Be careful
not to shorl Output 3 to any voltage pins or connections.
TB2 TRIGGER CONNECTOR ASSIGNMENTS
Pin 1: AUX POWER
Pin 2: KEY
Pin 3: OUT 1 – FIRE/ARMED LED
Pin 4: Not Used
Pin 5: OUT 2 -PANIC/READY LED/REMOTE SOUNDER
Pin 6: OUT 3- BURG/GLASSBREAK RESET
Pin 7: Not
Used
Pin 8: GROUND (-)
The table below describes the operation of the 3 output triggers. Address 1
●57
determines the trigger operation mode. Note that to use the 4146 Keyswitch,
only trigger modes “O”and”1” may be used.
—
ADDRESS —
1*57
*15
Trigger
Trigger
Trigger
Trigger Mode
Keyswitch
output 1
output 2 output 3
0 0 FIRE LRR PANIC LRR
TRIGGER
TRIGGER
BURG LRR
1
KEYSWITCH
KEYSWITCH
TRIGGER
ARMED LED READY LED
1
0
FIRE LRR
PANIC LRR
TRIGGER
TRIGGER ZONE 6
GLASS
1
KEYSWITCH
KEYSWITCH
BREAK
ARMED LED
READY LED RESET
2
0
FIRE LRR REMOTE
BURG LRR
1 not allowed TRIGGER
SOUNDER TRIGGER
3 0
FIRE LRR
REMOTE ZONE 6
1 not allowed TRIGGER
SOUNDER GLASS
BREAK
RESET
NOTE: IF ADDRESS 1*57 1SSET FOR 2 OR 3, ADDRESS ●15 MUST BE O.
-19-