REPORT CODE FORMATS
The following table describes the communication formats.
FORMAT TYPE DESCRIPTION
3+1 and 4+1
Standard Formats
Ex. SSS(S) A
Comprises a 3- (or 4-) digit subscriber number and a single-digit report code (e.g., Alarm,
Trouble, Restore, Open, Close, etc).
Ex.
S = Subscriber ID; A = Report Code
3+1 and 4+1
Expanded Formats
Ex. SSS(S) A
AAA(A) Z
Comprises a 3- (or 4-) digit subscriber number and a two-digit report code. The first digit
is displayed on the first line. The first digit is repeated on the second line 3 (or 4) times
followed by the second, expanded digit.
Ex. S = Subscriber ID; A = Report Code1st digit; Z = Typically Zone Number2nd digit
4+2 Format
Ex. SSSS AZ
Comprises a 4-digit subscriber number and 2-digit report code.
Ex.
S = Subscriber ID; A = Report Code; Z = Typically Zone Number)
ADEMCO Contact ID
Reporting Format
Ex. CCCC Q EEE GG ZZZ
Comprises a 4- or 10-digit subscriber number (depending on format selected), 1-digit
event qualifier (new or restore), 3-digit event code, and 3-digit zone number, user
number, or system status number (see below for example explanation).
ADEMCO Contact ID®
The ADEMCO Contact ID
®
Reporting Format comprises the following:
4-digit or 10-digit subscriber number (depending on format selected).
1-digit event qualifier (new or restore).
3-digit event code.
2-digit Partition No.
3-digit zone number, user number, or system status number (see table below).
ADEMCO Contact ID
®
Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ
where: CCCC(CCCCCC) =Customer (subscriber) ID
Q = Event qualifier, where: E = new event , and R = restore
EEE = Event code (3 hexadecimal digits)
GG = Partition Number (system messages show 00)
ZZZ = Zone/contact ID number reporting the alarm, or user number for open/close reports.
System status messages contain zeroes in the ZZZ location.
TABLE OF CONTACT ID EVENT CODES
(Some event codes may not apply to certain control panels;
for a complete list of event codes, refer to the central office receiver manual)
Code Definition
110 Fire Alarm
121 Duress
122 Alarm, 24-hour Silent
123 Alarm, 24-hour Audible
131 Alarm, Perimeter
132 Alarm, Interior
134 Alarm, Entry/Exit
135 Alarm, Day/Night
143 Alarm, Expansion Module
145 ECP Module cover tamper
146 Silent Burglary
150 Alarm, 24-Hour Auxiliary/Monitor zone
162 Carbon Monoxide
301 AC Power
302 Low System Battery/Battery Test Fail
305 System Reset (Log only)
321 Bell/Siren Trouble
333 Trouble, Expansion Mod. Supervision
341 Trouble, ECP Cover Tamper
344 RF Receiver Jam
351 Telco Line Fault
353 Long Range Radio Trouble
354 Failure to Communicate (log only)
373 Fire Loop Trouble
374 Exit Error Alarm
380 Global Trouble, Trouble Day/Night
381 RF Sensor Supervision
382 Supervision Auxiliary Wire Zone
Code Definition
383 RF Sensor Tamper
384 RF Sensor Low-battery
393 Clean Me
401 Disarmed, Armed AWAY, Armed MAXIMUM
403 Schedule Arm/Disarm AWAY
406 Cancel by User
407 Remote Arm/Disarm (Downloading)
408 Quick Arm AWAY
409 Keyswitch Arm/Disarm AWAY
441 Disarmed/Armed STAY/INSTANT,
Quick-Arm STAY/INSTANT
442 Keyswitch Arm/Disarm STAY
455 Scheduled Arm Fail
459 Recent Closing (SIA panels only)
570 Bypass
601 Manually Triggered Dialer Test
602 Periodic Test
606 AAV to Follow
607 Walk Test Entered/Exited
623 Event Log 80% Full
625 Real-Time Clock was Changed (log only)
627 Program Mode Entry (log only)
628 Program Mode Exit (log only)
642 Latch Key (log only)
750 -
789
Reserved for Configurable Zone Type report
codes (check with central station when using
these codes)