Installation Instructions
5-12
C
01 Enter Zn No.
12
Zone Number
If zone number was selected, this screen appears.
Enter the desired zone number associated with this output number.
Press [
] to continue.
Enter the zone event that will activate this output.
01 Enter Event 0 = restore; 1 = alarm
Restore 0 2 = fault; 3 = trouble
Press [
] to continue to the “Output Action” prompt
01 Output Action
Close for 2 sec 1
Output Action
0-6 = see list at right
Enter the desired device action as listed below. Press the [
] key to
continue.
0 = off 4 = Change Device State
1 = Close for 2 seconds 5 = Duration 1 (see data field *177
)
2 = Close and Stay Closed 6 = Duration 2 (see data field *177
)
3 = Pulse 1 sec ON, 1 sec OFF
† Duration 1:see data field *177 entry 1, from 15 secs to 15 minutes;
Duration 2: see data field *177 entry 2, from 1 to 7 days
Enter Output No.
R02 02
Output Number
01-16 = output no.
17-18 = on-board triggers
Enter the device output number (programmed in *79 Menu Mode)
you want associated with this output.
Press [
to continue.
02 A E P TRIG
R02 1 1 3 ZL=1
Summary Screen
A summary screen appears showing the programmed settings.
Press [
] to continue.