ADEMCO VISTA-48D Especificaciones Pagina 51

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 80
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 50
5-9
Start Output Device Mapping by pressing *79 while in Data Programming Mode. The following
prompts are displayed:
79 Menu Mode
PROMPT
VALID ENTRIES EXPLANATION
ENTER OUTPUT NO.
00 = QUIT xx
Device Output Number
01-18 = relays/X-10
[] to continue
This is the logical (or reference) relay number as used in the system.
Relays and X-10 devices are numbered 01-16; the on-board triggers
are numbered 17 and 18 and can be programmed for inverted output.
Use the worksheet on the Programming Form (printed separately) to
organize device numbers.
17 OUT NORM LOW
0 = NO 1 = YES 0
Output Normally Low
0 = no (standard default)
1 = yes
[] to continue
This prompt appears only for triggers 17 and 18.
Selecting 0 (no) sets the output level normally high.
Selecting 1 (yes) sets the output normally low.
Output trigger 17 can be used for resetting 4-wire smoke detectors by
connecting it to the negative power terminal of the smoke detector,
selecting 1 at this prompt, and setting as zone type 54, fire zone reset,
in *80 Menu mode.
After entry, display returns to Output Number prompt. Use *80
Menu mode to program the function of the trigger.
XX OUTPUT TYPE
DELETE 0
Output Type
0 = delete
1 = relay on 4204/4229 module
or 6164 keypad
2 = Powerline Carrier device
[] to continue
Select whether this is a relay or a Powerline Carrier (X-10) device.
If relay is selected, skip to “B” prompt.
If X-10 is selected, go to “A” prompt.
“A
XX UNIT No.
yy
Unit Number
01-16 = predefined address
[] to continue
If X-10 is selected, a prompt for the unit number appears.
Enter the unit code (set at the device) and press [].
The system returns to the Output Number prompt.
“B”
XX MODULE ADDR
07-15 yy
Module Address
07-15 = predefined address
[] to continue
If relay is selected, this prompt appears.
Enter the predefined address for this module as listed below. Make
sure the module’s DIP switches are set to the selected address (6164
keypad address is entered via its keypad programming prompts).
Module Addresses
Address Module or Keypad
07 1st 4229 (with zones 09-16) or 1st 6164
08 2nd 4229 (with zones 17-24) or 2nd 6164
09 3rd 4229 (with zones 25-32) or 3rd 6164
10 4th 4229 (with zones 33-40) or 4th 6164
11 5th 4229 (with zones 41-48) or 5th 6164
12 1st 4204
13 2nd 4204
14 3rd 4204
15 4th 4204
XX REL POSITION
1-4 zz
Relay Position
1-4 = relay position
[] to continue
This is the actual (or physical) relay number with respect to the Relay
Module upon which it is located. For 4204 modules, relay numbers
are 1-4. For 4229 modules, relay numbers are 1-2; for 6164 the relay
number is 1.
The system returns to the Output Number prompt for programming
the next device.
Vista de pagina 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 79 80

Comentarios a estos manuales

Sin comentarios