
Mounting and Wiring the Control
2-13
On-Board Triggers
Connect field wiring to the desired trigger pin on the
8-pin trigger connector centrally located above the
terminal strip.
• If using a Powerline Interface Modulator and
powerline carrier devices, use the SA4120XM-1
cable (part of 4120TR Trigger Cable). See previous
Powerline Carrier Device section.
• If only using the on-board triggers, you can use a
4-wire cable (N4632-4, supplied with the control) as
shown below.
1345678
SA412OXM-1
CABLE
8-PIN TRIGGER CONNECTOR
KEY
00-trigcon-003-V1
+12 AUX.
DATA
COM
SYNC
GND (-)
OUTPUT 17
(RED)
OUTPUT 18
(GREEN)
(ORANGE)
(YELLOW)
(BLUE)
(PURPLE)
(BLACK)
Figure 12. On-Board Trigger Connector with
SA4120XM-1 Cable for Use With X10 Powerline Interface
Modulator
4-WIRE
CABLE
00-trigcon-005-V2
+12 AUX.
GND (-)
OUTPUT 17
OUTPUT 18
(RED)
(YELLOW)
(BLACK)
(GREEN)
1345678
8-PIN TRIGGER CONNECTOR
KEY
Figure 13. On-Board Trigger Connector with
4-Wire Cable for Trigger Use Only
Notes
• There are two on-board triggers that can be
used to activate output devices.
• These outputs are normally high, and go low
upon programmed condition.
• The outputs can be programmed for inverted
operation (normally low, go high) using *79
Menu mode.
• Program these triggers using *80/*81 Menu
modes as you would for any other relay output.
• When using these outputs, note:
pin 1 = output number 17 (trigger 1):
15 ohms to ground when closed
(output low), open when off (output
high, normal default); can be used to
reset smoke detector power (must set
“output normal low = yes” in *79
Menu mode, and set for zone type 54,
fire zone reset, in *80 Menu mode); or
can support 12V relay module that
draws less than 100mA
pin 5 = output number 18 (trigger 2):
15 ohms to ground when closed
(output low); open when off (output
high, normal default); or can support
12V relay module that draws less than
20mA.
• NOTE: Do not exceed 120mA combined
current for both triggers. Doing so can
damage PC board components and will
void the system’s warranty.
UL
If on-board triggers are used, the wiring
between the control unit and the UL Listed device
must be run in conduit, be no more than 1 meter
apart and have no intervening barriers or walls.
Comentarios a estos manuales