Installation Instructions
4-4
FIELD
TITLE and DATA ENTRIES EXPLANATION
*44
Part. 1 Secondary Subs. Acct. No.
Enter digits 0–9; # + 11 for B, # + 12 for C, #
+ 13 for D, # + 14 for E, # + 15 for F.
Enter up to 10 digits, depending on the report format selected in field
*48. To clear entries from field, press ∗44∗.
*45
Part. 2 Primary Subs. Acct. No.
Enter digits 0–9; # + 11 for B, # + 12 for C, #
+ 13 for D, # + 14 for E, # + 15 for F.
Enter up to 10 digits, depending on the report format selected in field
*48. To clear entries from field, press ∗45∗.
*46
Part. 2 Secondary Subs. Acct. No.
Enter digits 0–9; # + 11 for B, # + 12 for C, #
+ 13 for D, # + 14 for E, # + 15 for F.
Enter up to 10 digits, depending on the report format selected in field
*48. To clear entries from field, press ∗46∗.
*47
Phone System Select/Dialer
Attempts
Phone System Select:
If Central Station Receiver is not on satellite
link: 0 = Decadic Pulse Dial;
1 = Multifrequency Tone Dial
If Central Station Receiver is on satellite link:
2 = Decadic Pulse Dial;
3 = Multifrequency Tone Dial
Dialer Attempts: 1 – 10 (for 10, enter #+10)
Phone System Select: Select the type of telephone service.
Dialer Attempts: Enter the number of times the system should
attempt to dial the central station, 1 – 10 times (for 10, enter #+10).
*48
Report Format (Primary/Secondary)
0 = 3+1, 4+1 ADEMCO L/S STANDARD
1 = 3+1, 4+1 RADIONICS STANDARD
2 = 4+2 ADEMCO L/S STANDARD
3 = 4+2 RADIONICS STANDARD
5 = CID* using 10-digit account number
6 = 4+2 ADEMCO EXPRESS
7 = CID* using 4-digit account number
8 = 3+1, 4+1 ADEMCO L/S EXPANDED
9 = 3+1, 4+1 RADIONICS EXPANDED
10 = ROBOFON 8 (6-digit account number)
11 = ROBOFON Contact ID
Select report format for primary and secondary phone numbers.
* ADEMCO Contact ID format
NOTE: To enable the audio “beeps” format (Follow-Me feature), refer
to the System Features section later in this manual, and the User
Guide.
*49
Split/Dual Reporting
0 = disable (standard/backup report only).
1 - 5 (see table to right)
To Primary No. To Secondary No.
1 = alarms, restore, cancel others
2 = all except open/close, test open/close, test
3 = alarms, restore, cancel all
4 = all except open/close, test all
5 = all all
*50
Burglary Dialer Delay
0 = no dial delay (UL: must be “0”)
1 = 15 seconds
2 = 30 seconds
3 = 45 seconds
Provides delay of “BURGLARY ALARM” report to the central station,
which allows time for the subscriber to avoid a false alarm
transmission. This delay does not apply to zone type 24 alarms (silent
burglary) or to 24-hour zone types 6, 7, and 8 (silent panic, audible
alarm, auxiliary alarm), which are always sent as soon as they occur.
*51
Part. 3 Primary Subs. Acct. No.
Enter digits 0–9; # + 11 for B, # + 12 for C, #
+ 13 for D, # + 14 for E, # + 15 for F.
Enter up to 10 digits, depending on the report format selected in field
*48.
*52
Part. 3 Secondary Subs. Acct. No.
Enter digits 0–9; # + 11 for B, # + 12 for C, #
+ 13 for D, # + 14 for E, # + 15 for F.
Enter up to 10 digits, depending on the report format selected in field
*48.
*53
SESCOA/Radionics Select
0 = Radionics (0-9, B-F reporting)
1 = SESCOA (0-9 only reporting)
Select SESCOA or Radionics format.
Select 0 for all other formats.
*54
Dynamic Signaling Delay
0 = disabled (both signals sent)
1–15 = entry times a 15-second delay.
e.g., 1 = 15 seconds, 2 = 30 seconds, etc.
Intended for use with ECP Contact ID Output reporting via ACM.
This field lets you select the time the panel should wait for
acknowledgment from the first reporting destination (see ∗55) before
it attempts to send a message to the second destination. Delays can
be selected from 0 to 225 seconds, in 15-second increments. This delay
is per message. If ”0” is entered in this field, the control panel will
send redundant reports to both Primary Dialer and ECP output.
UL Installations: For Fire Alarm and UL Burglar Alarm installations
without Line Security (Grade A), the maximum Dynamic
Signaling Delay must be no more than 15 seconds.
For UL Burglar Alarm installations with Line Security (Grade
AA), Dynamic Signaling Delay must be “0”. The reports will be sent to
both the dialer and the LRR.