Installation Instructions
5-2
PROMPT
VALID ENTRIES EXPLANATION
10 Zone Type
Perimeter 03
Zone Type (ZT)
00-24, 77, 82, 90-93 = zone
type (see table at right)
Each zone must be assigned to a zone type, which defines the way in
which the system responds to faults in that zone.
Enter the Zone Type code from the list below:
Note: If 00 is entered, Delete Zone ? will be displayed.
00 = Not used 07 = 24-Hr Audible 20 = Arm–STAY*
01 = Entry/exit #1 08 = 24-Hr Aux 21 = Arm–AWAY*
02 = Entry/exit #2 09 = Fire 22 = Disarm*
03 = Perimeter 10 = Interior w/Delay
23 = No Alarm Resp
04 = Interior Follower 12 = Monitor Zone 24 = Silent Burglary
05 = Trouble Day/Alarm Night 14 = Gas 77 = Keyswitch
06 = 24-Hr Silent 16 = Fire w/Verify 81 = AAV Monitor Zone
82 = Blockschloss
*5800 button-type transmitters only 90-93 = Configurable
10 Partition
1
Partition No. (P)
1-3 = partition
[∗] to continue
Enter the Partition number for this zone. Partition 1 is shown
entered.
10 Report Code
1st 01 2nd 00 10
Report Code (RC)
First Digit: 1-9, 10 for 0, 11 for
B, 12 for C, 13 for D,
14 for E, 15 for F
00 to disable
Second Digit: same as above
[∗] to continue
Enter the report code for this zone, which consists of 2 hexadecimal digits,
each in turn consisting of 2 numerical digits. For example, for a report code
of “10,” enter 01 and 00.
For Contact ID
®
, entering any non-zero entry as the first digit enables the
report code for this zone. Refer to the System Communication section for
information about report codes and formats.
02 HARDWIRE TYPE
EOL 0
Basic Wired Type
0 = EOL; 1 = NC; 2 = NO
3 = zone doubling (ZB)
4 = double-balanced (DB)
[∗] to continue
This prompt appears only for zone numbers 02-08.
Zone 1 is automatically set for EOL operation.
02 Response Time
1
Response Time (RT)
0 = 10mSec 2 = 700mSec
1 = 400mSec 3 = 1.2 seconds
[∗] to continue
This prompt appears only for basic wired zones 01-08 (zone 02 is used
as an example in display).
NOTE: If zone doubling is being used, the response time set for zones
01-08 automatically applies to each zone’s associated doubled zone.
10 INPUT TYPE
RF TRANS 3
Input Device type (In)
2 = AW (Aux wired zone)
3 = RF (supervised RF
transmitter,
4 = UR (unsupervised RF
transmitter)
5 = BR (unsupervised button
type RF transmitter)
7 = RM (supervised RF motion
detector)
[∗] to continue
This prompt is skipped for zones 9-16 if zone-doubling was enabled at
“Hardwire Type” prompt.
All of the RF transmitters have one or more unique factory-assigned
input (loop) ID codes. Each of the inputs requires its own
programming zone (e.g., a 5804's four inputs require four
programming zones).
RF Transmitters can be enrolled as one of the following types:
Type Description
“RF” Sends periodic check-in signals, as well as
(Supervised RF) fault, restore, and low-battery signals. The
transmitter must stay within receiver's range.
“UR” Sends all the signals that the “RF” type
(Unsupervised RF) does, but the control does not supervise the
check-in signals. The transmitter may therefore
be carried off-premises.
“BR” (Unsupervised Sends only fault signals. It does not send a
Button RF) low-battery signal until it is activated. The
transmitter may be carried off-premises.
“RM” Sends periodic check-in signals, as well as fault
(Supervised RF and low- battery signals. The panel ignores
Motion Detector) detector restore signals but automatically
restores the zone to “ready” after a few seconds.
Designed for facilities with multiple motion
detectors that may fault and restore
simultaneously. The transmitter
NOTES: must remain within the receiver’s range.
• For the built-in basic wired zones, the Input Device type is
automatically displayed as HW and cannot be edited.
• To change the input type of a previously programmed wireless
device (type RF, UR, BR, RM) to a wired zone (type AW), you must
first delete the transmitter’s serial number