VISTA-100 Installation Instructions
7-2
number or group is determined by the setting of DIP switches. Other devices have a built-in
unique serial number which must be programmed into the control as its zone number. To
set up the polling loop, take the following steps:
1. Run wires to each device on the polling loop. No individual wire run may exceed the
lengths given in the following table. In addition, no more than 64mA may be drawn on
any individual wire run. When a star configuration is used, the total length of all wire
runs combined cannot exceed 4000 ft (2000 ft. if using unshielded wire in conduit or
shielded wire). Twisted pair is recommended for all normal wire runs.
Maximum Polling Loop Wire Runs
Wire Gauge Max. Length
#22 gauge 650 feet
#20 gauge 950 feet
#18 gauge 1500 feet
#16 gauge 2400 feet
When running polling loop wires, do not run them within 6 inches of AC power, telephone, or
intercom wiring. Since the polling loop is carrying data between the control panel and the devices,
interference on this loop can cause an interruption of this communication. The polling loop can
also cause outgoing interference on the intercom or phone lines. If this spacing cannot be
achieved, shielded wire must be used. (Note that the maximum total wire length supported is cut
in half when shielded wire is used.)
2. Wire each device to the polling loop, making sure to use correct polarity when making
connections (refer to the device's instructions). If you are using serial number
devices, and you intend to have the control program each serial number
automatically, wire no more than 25 of these devices to the control at a time.
Then power up and program them (as described later in this section) before connecting
the next 25. Leave previously programmed devices connected.
3. If you intend to enter the serial numbers manually through the keypad or through V-
LINK downloading software, all the devices may be connected before powering up to
program them.
4. Note the polling loop devices that have DIP switches on them. Set each device's DIP
switches for the zone number you are assigning to it. Refer to the device's instructions or
the DIP Switch Tables in Appendix B when setting addresses.
Certain polling loop devices, such as the 4193SN and 4191SN, do not have DIP switches.
Instead, they have embedded serial numbers which must be programmed into the control
during #93 Menu Mode Zone Programming.
Certain polling loop devices have a DIP switch that can be used either to select the device's zone
number or to select the programming of a unique, embedded serial number into the control panel.
When used with VISTA-100, these devices
must
be set for the serial number mode of operation.