Section 1 - General Description
1-xv
Auxiliary Relay
Provides a built-in Form C relay which can be used for one of the following purposes:
Alarm activation
Trouble/supervisory activation
4-wire smoke detector reset
Battery-saving feature (disconnects power from noncritical loads 4 hours after AC power
loss)
Optional Output Relays
Accommodates the use of 16 relay outputs using ADEMCO's 4204 and 4204CF Relay
Modules. Each 4204 module provides four Form C relays for general-purpose use. Each
4204CF provides two style Y supervised bell outputs. Relay outputs have the following
characteristics:
Can be programmed to activate in response to system events
Can be programmed to activate using time intervals
Can be used for additional style Y supervised bell outputs (4204CF only)
Can be activated manually using the #70 relay command mode
Can be supervised by the control panel (zones 601-632)
Can each have an alpha descriptor assigned to it
Optional VISTA Interactive Phone Module
Supports the ADEMCO 4285/4286 VIP Module. This allows the security system to perform
the following tasks:
Obtain system status information
Arm and disarm security system
Control relays
U
L
The 4285/4286 VIP Module is not UL Listed for use with the VISTA-100 control panel
.
Access Control
If programmed, provides users with a command which activates a relay for 2 seconds to
open access doors (e.g., lobby door). Each partition can be assigned an access control relay.
U
L
The access control function is not UL Listed for use with the VISTA-100 control panel.
Optional 24-Volt Power Supply
Compatible with the PS24 Power Supply Module, which supplies:
Two 24VFW, 1.7A full-wave rectified, unfiltered outputs
Used to power alarm notification appliances (sirens, strobes, etc.)
Used to power auxiliary devices which can operate using full-wave rectified, unfiltered
voltage