VISTA-10SE Installation and Setup Guide
64
PROMPT VALID ENTRIES EXPLANATION
02 Stop: Zn List
No List 0
STOP by Zone List
[
]
to continue
If a zone list will be used to STOP, or restore, the relay action,
enter the zone list (ZL) number 1, 2, or 3 (to be programmed in
81 mode). If not used, enter 0.
02 Stop: Zn Typ
Not Used 00
STOP by Zone Type
[
]
to continue
If a zone type or system operation will be used to STOP the relay
action, enter the appropriate two digit code (see the "ZT" choices
listed above). If not, enter 00.
02 A EV ZL ZT
STT 0 0 0 00
START Summary Screen
[
]
to continue
This screen displays a summary of the current relay START
programming.
02 A EV ZL ZT
STP 0 0 0 00
STOP Summary Screen
[
]
to continue
This screen displays a summary of the current relay STOP
programming.
Enter Relay No.
(00 = Quit) 01
The display then returns to the first screen so that the next relay number to be
programmed can be entered, unless you enter [0][0] to end relay programming.
Previously entered data can be reviewed by pressing [#] [8] [0]. After the relay number is
chosen, press [
] to go to the next screens. This is a review mode only, and data cannot be
changed.
Example of Relay Programming
A lamp is to be turned on when any one of three specific zones are faulted or when any 24-hour
auxiliary zone is faulted. We want to turn off the lamp manually without affecting the arming
status of the system.
In field
80, we choose Relay 01 and program the Action (A) to be "2" (Close and stay closed). The Event we
are looking for to START the relay action is a fault, so we program "2" in (EV). We will use Zone List 1 for
the 3 specific zones, so we program "1" in (ZL), (these 3 zones are programmed in field
81's Zone List 1).
The second condition for turning on the indicator is triggering a 24-hour auxiliary zone (Zone Type 08), so we
program (ZT) as "08."
To STOP relay action and turn off the indicator, we do not want to use a restore of any zone, so we will
program a "0" for the "Restore of" Zone List (ZL). To choose a manual entry of User Code + [#] + [7] to turn it
off, we will program (ZT) as "34."
If no other relay is to be programmed, we go to field
81 and program the 3 specific zones in Zone List 1.
Press
81. (Zone Lists for Output /Relays). This interactive mode is applicable only if you have programmed
80 mode.
Refer to, OUTPUT RELAYS WORKSHEET FOR FIELDS
80 and
81 in the Programming Form, to
record data.