VISTA-10SE Installation and Setup Guide
2-4
+
–
+
456 7
SUPPLEMENTARY
POWER SUPPLY
–
CONTROL TERMINAL STRIP
AUX.
AUX. DATA
IN
DATA
OUT
IMPORTANT:
MAKE THESE
CONNECTIONS
DIRECTLY TO
SCREW
TERMINALS AS
SHOWN.
TO KEYPAD RED WIRE
TO KEYPAD BLK WIRE
TO KEYPAD YEL WIRE
TO KEYPAD GRN WIRE
TO KEYPAD BLK WIRE
TO KEYPAD RED WIRE
TO KEYPAD GRN WIRE
TO KEYPAD YEL WIRE
supp_pwr_supply-V0
Figure 2-5. Using a Supplementary Power Supply for Keypads
Sounder (Bell) Connections
1. Make sounder connections to alarm output
terminals 3 (+) and 4 (–) on the control panel.
+
+
3
4
NO. 702
SIREN
CONTROL
BOARD
ALARM
OUTPUT
sounder_wir-V0
Figure 2-6. Typical Sounder Wiring
For supervised output, continue with steps 2 and 3.
2. Cut the red Bell Supervision Jumper located above
terminals 2 and 3 on the control board as indicated
in Figure 2-7.
3. Connect a 1k ohm resistor across the terminals of
the last sounder, not across the control's terminals.
This control complies with NFPA requirements for
temporal pulse sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of:
3 pulses – pause – 3 pulses – pause – 3 pulses–etc.
+
+
3
4
OBSERVE
POLARITY
TERMINALS ON
CONTROL BOARD
ALARM
OUTPUT
TERMINALS
CUT RED JUMPER ON
CONTROL BOARD
TO ENABLE BELL
(SOUNDER) SUPERVISION
IF BELL SUPERVISION IS ENABLED (RED JUMPER
ON CONTROL BOARD IS CUT), CONNECT A 1000
OHM RESISTOR ACROSS THE EXTERNAL
SOUNDER, AS SHOWN BY THE DASHED LINE.
DO NOT CONNECT THE RESISTOR AT THE
ALARM OUTPUT TERMINALS THEMSELVES!
EXTERNAL
ALARM
SOUNDER
1000
OHM
EOL
RESISTOR
bell_suprv_wir-V0
Figure 2-7. Sounder Wiring (Supervised)
NOTES:
•
The 12VDC sounder output activates when an
alarm occurs.
•
Total current drawn from this output cannot exceed
2 amps (going beyond 2 amps will overload the
power supply, or may cause the electronic circuit
protecting the sounder output to trip).
•
You must install a battery, since the battery
supplies this current.
U
L
•
Use only UL Listed sounding devices for UL installations mounted indoors.
•
The total current drawn from the alarm output and the
auxiliary power output, combined, cannot exceed
600mA. In addition, the sounding device must be a UL Listed audible signal appliance rated to operate
in a 10.2-13.8 VDC voltage range, and must be mounted indoors.
Wiring the AC Transformer
1321 Transformer
Wire the 1321 Transformer to terminals
1
and
2
on the
control board. Refer to wiring table at right for wire
gauge to use.
WIRING TABLE
Distance of Transformer
From the Control Panel
Wire Gauge
to Use
Up to 50 feet # 20
50 – 100 feet # 18
100 – 250 feet # 16