Section 3 Programming Overview
3-3
Mechanics of Programming
To program the system from a keypad:
You must use a 2-line Alpha display keypad.
The panel must be disarmed.
Data Field Programming Procedures
Task Procedure
Enter Program Mode
A) Press both [
] and [#] at the same time within 50 seconds after power is applied to
the control,
OR
B) After power-up, enter [Installer code (4-1-1-1)] + 8 + 0.
(method B is disabled if you exit the program mode using
98)
Go to a Data Field
Press [
] + [Field Number] (for example,
21).
A display of EE or Entry Error means you have entered a nonexistent field.
Simply reenter [
] plus a valid field number.
Enter Data
When the desired field number appears, simply enter the digits required. The keypad
beeps three times after the last digit is entered and automatically displays the next
data field in sequence.
If entering less than the maximum digits available (e.g., phone number field), enter
the desired digits, then press [
] and the next data field number to be programmed,
to end the entry.
Review a Data Field
Press [#] + [Field Number].
That fields data is displayed, but no changes can be made.
Delete an Entry in a Field
Press [
] + [Field No.] + [
] (applies only to primary/secondary phone number,
subscriber account number, and download telephone number fields).
Interactive Mode Programming (
56,
58,
80,
81, and
82)
Enter Interactive Mode
Press
[
] +
[Interactive Mode No.] (for example,
56) while in Program Mode. The
Alphanumeric display keypad will display the first of a series of prompts requesting
entries.
After making the appropriate entry, press the
[
]
key to accept the entry and
continue to the next prompt.
Loading Factory Defaults/Initializing for Download
To Load Default Entries
Press
97 while in Program Mode. This resets all data fields to the factory default
values (if any). Use
97
only if you wish to return to the original factory-programmed
defaults.
To Initialize Download ID
Press
96 while in Program Mode. This initializes the system for downloading and
resets all the subscriber account numbers and CSID.
Do not press
97 to load defaults if any programming has been done previouslydata already programmed into
the system will be changed!
Exiting the Programming Mode
Prevent Installer code reentry
Press
98. Exits Programming Mode and prevents reentry by:
Installer Code + [8] + [0]. To enter the programming mode if
98 was used to exit,
you must first power the system down. Then power up again, and press
[
]
and [#] at
the same time, within 50 seconds of powering up.
Allow Installer code reentry
Press
99. Exits Programming Mode and allows reentry by:
Installer Code + [ 8] + [0] or by: Pressing
[
]
and [#] at the same time, within 50
seconds of powerup.
Vista de pagina 22