VISTA-250FBP (3/17/2003) 13850 - 8
Detection and Alarm
e. ADEMCO 5869 Wireless Hold Up Switch/Transmitter - This
device shall be UL 636 listed for commercial burglary
applications.
15. Optional Keyswitch – The control shall support the ADEMCO 4146
Keyswitch on any one of the system's 8 partitions. If used, zone 7 is no
longer available as a protection zone.
16. Voltage Triggers – The system shall provide voltage triggers, which
change state for different conditions. Used with LRR (Long Range
Radio) equipment or other devices such as a remote keypad sounder,
keyswitch ARMED and READY LEDs, or a printer to print the system's
event log.
17. Event Log – The System shall maintain a log of different event types
(enabled in programming). The event log shall provide the following
characteristics:
a. Stories up to 1,000 events.
b. Viewable at the keypad or through the use of Compass software.
c. Printable on a serial printer using a 4100SM Module including
zone alpha descriptors.
d. Stores PassPoint access control events.
e. Sends printed events to up to eight alpha numeric pagers.
18. Scheduling - Provides the following scheduling capabilities:
a. Open/close schedules (for control of arming/disarming and
reporting).
b. Holiday schedules (allows different time windows for open/close
schedules).
c. Timed events (for activation of relays, auto-bypassing and un-
bypassing, auto-arming and disarming, etc.).
d. Access schedules (for limiting system access to users by time)
e. End User Output Programming Mode (provides 20 timers for relay
control).
f. The system shall automatically adjust for daylight savings time.
19. Communication Features - Supports the following formats and features for
the primary and secondary central station receivers:
a. Formats
(1) ADEMCO Low Speed (Standard or Expanded).