VISTA-250FBP (3/17/2003) 13850 - 3
Detection and Alarm
A. Control Panel - The control panel shall be an eight (8)-partition, UL commercial
fire and burglary control panel that supports up to 250 zones using basic
hardwired, polling loop, and wireless zones. It shall also provide supervision of
two (2) notification appliance output circuits (NAC), RF receivers, and relay
modules. In addition, the control shall provide the ability to schedule time-driven
events, and allow certain operations to be automated by pressing a single button.
The system shall be capable of interfacing with an ECP long range radio (LRR)
unit that can send Contact ID messages, and alphanumeric paging devices. The
control shall provide integrated access control and CCTV-switching capability
with the use of a single downloader and database.
1. Basic Hardwired Zones - The control shall provide eight (8) style-B
hardwire zones with the following characteristics:
a. EOLR supervision (optional for zones 2-8): Shall support N.O. or
N.C. sensors (EOLR supervision required for UL installations).
b. Zones/Points shall be individually assignable to any partition.
c. Supports up to 64 two-wire smoke detectors on two selected zones.
d. Supports four-wire smoke or heat detectors on any zone (power to
four-wire smoke detectors must be supervised with an EOL
device).
e. Supports up to 50 two-wire latching glass break detectors on one
selected zone.
f. Individually assignable to Notification Appliance (NAC) outputs
and/or auxiliary relays.
2. Optional Expansion Zones
a. Polling Loop Expansion The control shall support up to 242
additional hardwire zones using a built-in two-wire polling
(multiplex) loop interface. The polling loop shall provide power
and data to remote point modules, and constantly monitor the
status of all zones on the loop. Maximum current draw shall not
exceed 128 mA. The polling loop zones shall have the following
characteristics:
(1) Interface with RPM (Remote Point Module) devices that
provide Class B, Style Y (e.g., 4208U/4208SN) or a
combination of Class B, Style Y, and Class A, Style Z
(e.g., 4208SNF) zones.
(2) Individually assignable to one of eight (8) partitions.
(3) Supervised by the control panel.
(4) A 12,000 ft (3658 m) wire run capability without using
shielded cable.
Vista de pagina 3