FIELD TITLE and DATA ENTRIES EXPLANATION
*60
Trouble Report Code
0 = no report
1st digit non-zero = send report
This will be sent if a zone has a trouble condition.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*61
Bypass Report Code
0 = no report
1st digit non-zero = send report
This will be sent when a zone is manually bypassed.
UL: Required for UL commercial burglar alarm installations.
*62
AC Loss Report Code
0 = no report
1st digit non-zero = send report
Timing of this report is random with up to a 4-hour delay. If AC
restores before the report goes out, there is no “AC RESTORE”
report.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*63
Low Bat Report Code
0 = no report
1st digit non-zero = send report
Sent when a low-battery condition exists in the system’s battery.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*64
Test Report Code
0 = no report
1st digit non-zero = send report
Sent periodically to test that the communicator and phone lines are
operational. Frequency of report is set in Scheduling mode (event 11).
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*65
Open Report Code
0 = no report
1st digit non-zero = send report
This is sent upon disarming of the system in the selected partitions.
UL: Required for UL commercial burglar alarm installations.
*66
Arm Away/Stay Report Code
0 = no report
1st digit non-zero = send report
This option allows for independent programming of Away and Stay
reports for each partition, including the common lobby.
NOTE: “OPEN” reports are not sent if the associated closing report
is not enabled.
*67
RF Trans. Low Batt. Report Code
0 = no report
1st digit non-zero = send report
Sent when a wireless transmitter low-battery condition exists.
UL installations: must be enabled if wireless devices are used.
*68
Cancel Report Code
0 = no report
1st digit non-zero = send report
This is sent upon disarming of the system after an alarm condition
was reported.
Restore Report Codes (
∗
70–
∗
76)
FIELD TITLE and DATA ENTRIES EXPLANATION
*70
Alarm Restore Report Code
0 = no report
non-zero = send report
Sent when an alarm zone is restored to its non-faulted condition.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*71
Trouble Restore Report Code
0 = no report
1st digit non-zero = send report
This is sent when a trouble in a zone is restored
UL: Required for UL commercial burglar alarm installations.
*72
Bypass Restore Report Code
0 = no report
1st digit non-zero = send report
This is sent when a zone that has been bypassed is unbypassed.
UL: Required for UL commercial burglar alarm installations.
*73
AC Restore Report Code
0 = no report
1st digit non-zero = send report
Sent when AC power has been restored after an AC power outage.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*74
Low Bat Restore Report Code
0 = no report
1st digit non-zero = send report
Sent when a system low-battery condition is restored to normal.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*75
RF Xmtr Low Batt. Restore Code
0 = no report
1st digit non-zero = send report
Sent when a transmitter’s low battery condition is restored (i.e., new
battery installed).
UL installations: must be enabled if wireless devices are used.
Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*76
Test Restore Report Code
0 = no report
1st digit non-zero = send report
This is sent when the Test mode is exited.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.