Hardwire Zones
Normally Open Zones
1. Connect open circuit devices in parallel across the
loop, with the EOLR connected across the loop wires
at the last device.
2. Enable normally open/EOLR zones using Zone
Programming mode, “Hardwire Type” prompt.
Normally Closed Zones
1. Connect closed circuit devices in series in the high (+)
side of the loop, with the EOLR connected in series
following the last device.
2. Enable normally closed/EOLR zones using Zone
Programming mode, “Hardwire Type” prompt.
Double-Balanced (V20P only):
Connections as shown
(resistors not provided).
IMPORTANT:
Double-balanced zones provide zone tamper
protection, and should be used as burglary zones only. Do not
use double-balanced zones as fire zones.
Zone Doubling (V20P only):
Connections as shown.
2k
2k
2k
ZONE 3
2k
2k
2k
ZONE 4
12 13
14
zone-002-V0
TAMPER
CONTACTS
TAMPER
CONTACTS
10 11
6.2k
ZONE 10
3k
ZONE 2
zone-004-V0
Double Balanced Zones Zone Doubling
Notes
EOLR:
If the EOLR is not at the end of the loop,
the zone is not properly supervised and the
system may not respond to an “open” on the zone.
Zone 1 is intended for EOLR only.
U
L
For UL commercial burglar alarm
installations, use normally closed zones.
Zone Doubling (VISTA-20P only):
This feature provides two hardwired zones for each
standard hardwired zone connected to the control’s
terminals (but does not increase the total number
of zones supported by the control). If enabled (Zone
Programming mode, “Hardwire Type” prompt,
option “3”), hardwire zones are automatically
paired as follows:
Zone Paired with zone
210
311
412
513
614
715
816
Note for Configurable Zone Types:
A short
across the EOL (i.e., at terminal) on either zone of
a zone-doubled pair or on a double-balanced zone
causes a tamper condition
.
Smoke Detectors
2-Wire Smoke Detectors
1. Connect up to sixteen (10, if “clean me” option used)
2-wire smoke detectors across zone 1 terminals 8 (+)
and 9 (-) as shown in the Summary of Connections
diagram at the back this manual. Observe proper
polarity when connecting the detectors.
2. Connect EOL resistors across the loop wires at the
last detector.
4-Wire Smoke Detectors
3. Connect 4-wire smoke detectors to any zone from 2
and higher as shown below. This control does not
automatically reset power to 4-wire smoke detector
zones, so you must use a relay (4204, 4229, or
on-board trigger connected to separate relay) to reset
power. Do this by programming the designated
relay/trigger as zone type 54 (fire zone reset).
+
+
2000
OHMS
EOLR
HEAT
DETECTOR
RED
EOL
POWER
SUPERVISION
RELAY MODULE
A77-716B
VIOLET
AUX PWR
OUTPUT
TERMINALS
5
4
+
BLK
+
4wiresmk-001-V0
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
TO ZONE TERM. ( )
TO ZONE TERM. ( )
RELAY
PROGRAM RELAY
AS ZONE TYPE 54
(FIRE ZONE RESET)
Figure 7. 4-Wire Smoke Detector Connections
Notes
Fire Verification (zone type 16):
The control
panel will “verify” any alarm by resetting the
smoke detectors after the first alarm trigger, and
then waiting 90 seconds for a second alarm
trigger. If the smoke detector or thermostat does
not trigger again, the control will disregard the
first trigger, and no alarm signal will occur. This
feature eliminates false alarms due to electrical
or physical transients.
The zone 1 alarm current supports only one
smoke detector in the alarmed state.
Do not use 4-wire smoke detectors on zone 1.
Clean Me Option:
If enabled (field *174 = 1;
*56 zone programming, response type prompt =
3), certain ESL smoke detectors
send “clean me”
reports as appropriate. If used, the maximum
number of detectors is reduced to 10 (not
standard 16).
Refer to the ESL documentation included with
the smoke detector for information regarding
compatibility with the clean-me option.
Installation Instructions
2-6