Vista 20SEa Training Guide Page 8
3. Vista 20SEa Instruction Addendum
Duress
User code # 16 is a global Duress code. Entry of this code will generate a Contact ID
event code of 121 with a User # of 92. If used in conjunction with an Open or Close event,
it will also send an Open/Close by User #16.
Supervised Bell/Siren Output
By cutting the Red jumper above terminals 1 and 2, the alarm output can be supervised by
fitting a 2K-ohm resistor at the noisemaker. A short or open of the resistor will result in a
Check/Trouble display and Contact ID Event Code of E321.
Strobe Output
Connect negative of Strobe to pin 8 of the nine wa y connector located near the middle of
the circuit board.
Connect positive of Strobe to terminal 5 of the main terminal block.
No programming is required for the Strobe function.
Confirmation of Arming Ding Options
An additional option for sounding the noisemaker when the system has been armed with
an RF button is now available for either or both partitions. Program field *38 will now
accept an entry of 2 for this feature.
4 Wire Smoke Detectors
Smoke Detectors should be powered from the Programmable Trigger Output, pin 9 (-) and
pin 7 (+), with Program field *90 set to 2, Resettable Smoke Detector Power.
RF Jamming Supervision
The 5882 RF receiver supports RF Jam Detection. If field * 22 is set to 4, a continuous RF
transmission of greater than 30 seconds will generate a console display of RF Jam and a
Contact ID event code of 344 to be sent to the Central Station.
+ -
9 Way Pin Header
Below Heatsink
+ -
Strob
1
2
3
4
5
6
7
8
9
1 2 3
4
-
5
+
Vista 20SEa Main
Smoke Detector
Vista de pagina 7