3*20 TRIGGER OUTPUTS SELECTION [0]
0= LORRA full connection & Remote Console Sounder;
1=LORRA limited conn. & Keyswitch LEDs; 2=LORRA fire
only conn. & 5140LED
3*21 MAX # OF DIALER ATTEMPTS [8]
1-8 (3, 4 or 5 for NFPA72 compliant systems when a
secondary phone number is programmed (field *34)
3*30 DIALER SELECTION [1,0]
1=enabled; 0=disabled Main Backup
3*31 BACKUP DIALER TOUCHTONE/ROTARY [0]
1=TouchTone; 0=Rotary
3*50 ZONE TYPE RESTORE ENABLES
FOR ZONE TYPES 16-18 16 17 18
1 = enabled; [0 = disabled]
3*57 BELL 2 & AUX. RELAY CONFIRM
ARM DING Bell 2 AUX.
1=enable; [0=disable] . Must be 1 for UL Commercial
Burglary.
3*58 BELL 2 & AUX. RELAY AC POWER
LOSS ALARM 1=yes; [0=no] (must be "1" for UL)
3*59 ENABLE BELL 2 & AUX. RELAY
CHIME ANNUNCIATION Bell 2 AUX
1=enable; [0=disable]
3*60 BELL 2 & AUX. RELAY TIMEOUT | |
00-15 times 2 minutes; 00=no timeout [00,00] Bell 2 AUX
Must be minimum of 16 minutes for UL Burglary installations.
3*61 AUX. RELAY FUNCTION [1]
0=Trouble/supervisory; 1=Alarm, silenced by code + OFF
2=Smoke Detector Reset; 3=Battery Save; 4=Alarm, silenced
by code + [#] + 67
3*82 ENABLE BURG. FEATURES ON PART. 1 [1]
1=enable; 0=disable; “0” disables AWAY, STAY, MAX,
TEST, INSTANT & CHIME functions
3*85 ENABLE FIRE & SYSTEM ZONE BYPASS [1]
0=not enabled; 1=only installer can bypass]; 2=only installer &
master user can bypass. Applies to fire zone types 9, 16, 17 &
18 and system zones 70-77. Applies to Partition 1 only.
SUMMARY OF PROGRAMMING COMMANDS
To enter program mode, enter installer code +
[8] + [0] + [0]
To set standard defaults, press *97
To set communication defaults, press *94 +
one of the following: *80=low speed; *81=Ademco
Express; *82=Ademco High Speed; *83=Ademco's
Contact ID
To change to next page of program fields,
press *94
To return to previous set of fields, press *99
To erase account & phone number field
entries, press [*] + field number + [*]
To assign zone descriptors, press #93 +
follow menu prompts
To add custom words, press #93 + follow menu
prompts
To enter Installer's Message, press #93 +
follow menu prompts
To exit program mode, press *99 OR *98: *99
allows re-access to programming mode by installer
code. *98 prevents re-access to programming
mode by installer code.