11. Install Wireless Transmitters
Select a House ID (all transmitters must be set to the same House ID as you will program
into the system). To determine a House ID that is not being used in a nearby system, use
the House ID Sniffer Mode (see Section 5: TESTING THE SYSTEM for further
instructions on using House ID Sniffer Mode).
Determine what zone response type each transmitter will represent.
Select each transmitter's zone number according to its zone response type (use the chart
below).
ZONE NUMBER (RF XMTR ID) ZONE TYPE
10-13 ENTRY/EXIT, Burg.
14-29 PERIMETER, Burg.
30-43 INT/FOLLOWER, Burg.
44, 45 INT w/DELAY, Burg.
46, 47 PERIMETER, Burg.
RF XMTR ID ZONE TYPE
48-55 FIRE
56-61 TROUBLE BY DAY/
ALARM BY NITE, Burg.
62 24 hr. (audible)
63 Programmed by field *92
Set DIP switches on transmitters (according to each transmitter's instructions) for the zone
numbers and House ID selected (see DIP Switch Settings for Wireless Devices on page 17 of
this manual. Do not set two transmitters for the same zone number.
Mark each transmitter's zone number so you can identify it easily when mounting.
Program House ID and transmitter zone numbers into the system (see program fields *24
and *76 thru *92).
Do not permanently mount transmitters until transmission from each location has been
verified (see Section 5: TESTING THE SYSTEM for instructions on performing the Go/No Go
Test Mode.
––––––––––––––––––––––– WIRING GUIDELINES –––––––––––––––––
Aux Power Wire Run Chart
TOTAL CURRENT DRAWN BY ALL DEVICES* CONNECTED TO A SINGLE
WIRE RUN
Wire Size 50 mA or less 51 - 100 mA 101- 300 mA 301 - 500 mA
#22 500 ft (152m) 250 ft (76m) 80 ft (24m) 50 ft (15m)
#20 750 ft (228.6m) 380 ft (116m) 130 ft (39.6m) 80 ft (24m)
#18 1300 ft (396m) 650 ft (198m) 220 ft (67m) 130 ft (39.6m)
#16 1500 ft (457m) 1000 ft (305m) 330 ft (100.5m) 200 ft (70m)
* Includes Keypads, RF Receiver, and alarm devices requiring separate power.
Example: If you have two motion detectors that draw a total of 44 mA, and you are
using #20 AWG wire, the distance from the control panel Aux + and -
terminals to the last device can be up to 750 ft.
IMPORTANT
The combined length of all wire runs for devices connected to the
keypad data lines must not exceed 1500 feet (457m) when unshielded
quad conductor
cable is used (750 feet if shielded cable is used). This
restriction is due to the capacitive effect on the data lines when quad
cable is used.
Transformer Wiring Table
Distance of Transformer Wire Gauge
From the Control Panel To Use
Up to 50 feet # 20
50–100 feet # 18
100–250 feet # 16