Tech Note
Honeywell Vista Panel Polling Loop Troubleshooting Guide
Table of Contents
G
ENERAL NOTES ....................................................................................................................................................... 2
R
ANDOM CHECK ON ZONES ...................................................................................................................................... 3
G
ENERAL NOTES
SMOKE MAINTENANCE FEATURE
POLLING LOOP AND OTHER VOLTAGE THRESHOLDS
WIRING
T
ROUBLESHOOTING
C
ONTINUOUS CHECK ON ZONES ............................................................................................................................... 4
S
LOW ZONE RESPONSE ............................................................................................................................................. 5
V-
PLEX SMOKE DETECTORS .................................................................................................................................... 6
V-
PLEX MOTION SENSORS ........................................................................................................................................ 6
Z
ONES WILL NOT FAULT ........................................................................................................................................... 6
C
HECK 97/997 (POLLING LOOP SHORT) ................................................................................................................... 7
L
IMITATIONS OF V-PLEX CABLE RUNS .................................................................................................................... 7
P
ROCEDURE FOR DETERMINING THE MAXIMUM WIRE LENGTH PER POLLING LOOP
W
IRING NOTES AND RECOMENDATIONS
U
SING THE 4297 POLLING LOOP EXTENDER MODULE (APPLIES TO PANELS WITH 128MA ON POLLING LOOP) ... 9
S
INGLE 4297 TO EXTEND POLLING LOOP .............................................................................................................. 11
U
SING THE VPLEX-VSI SHORT ISOLATOR .......................................................................................................... 11
G
ROUND FAULT TROUBLESHOOTING (APPLIES TO COMMERCIAL FIRE PANELS ONLY) .................................... 12
T
ROUBLESHOOTING
PREMISE/THEORY
NORMAL OPERATION
GROUND FAULT FAQ’S
Table of Figures
FIGURE 1: 4297 SUPPLEMENTARY POWER SUPPLY ................................................................................................................... 9
F
IGURE 2: USING MULTIPLE 4297'S .................................................................................................................................... 10
F
IGURE 3: SINGLE 4297 TO EXTEND POLLING LOOP ................................................................................................................ 11
List of Tables
TABLE 1: POLLING LOOP WIRING USING UNSHIELDED TWISTED (OR NON-METAL CONDUIT) .............................................................. 7
T
ABLE 2: POLLING LOOP WIRING USING SHIELDED (OR METAL CONDUIT) ONE SIDE OF THE SHIELD TO GROUND. ................................... 8
T
ABLE 3: GROUND FAULT VOLTAGES .................................................................................................................................... 13
Vista de pagina 0
1 2 3 4 5 6 ... 13 14

Indice de contenidos

Pagina 1 - Tech Note

- 1 - Updated: 8/17/12 Tech Note Honeywell Vista Panel Polling Loop Troubleshooting Guide Table of Contents GENERAL NOTES ...

Pagina 2

- 10 - Updated: 8/17/12 Tech Note Using Multiple 4297 Polling Loop Extenders

Pagina 3

- 11 - Updated: 8/17/12 Tech Note Single 4297 to Extend Polling Loop Figure 3: Single 4297 to Extend Polling Loop D1-i + … Dn-i

Pagina 4

- 12 - Updated: 8/17/12 Tech Note Ground Fault Troubleshooting (Applies to Commercial Fire Panels Only) Troubleshooting 1. Measure Volts DC

Pagina 5

- 13 - Updated: 8/17/12 Tech Note Premise/Theory The control panel internally causes its power negative to float 1 volt below earth ground a

Pagina 6

- 14 - Updated: 8/17/12 Tech Note Ground Fault FAQ’s 1. I have a Ground fault on my display. Does this mean that I have a bad earth ground?

Pagina 7

- 2 - Updated: 8/17/12 Tech Note General Notes 1. Do not connect/disconnect devices when the panel is live, may cause alarms and trouble co

Pagina 8

- 3 - Updated: 8/17/12 Tech Note Random Check on zones General Notes Global polling devices (such as 5192 or 998mx) MUST be set in serial n

Pagina 9

- 4 - Updated: 8/17/12 Tech Note Troubleshooting 1. If the device has the option to go serial, it must be in serial mode. 2. If using Dip

Pagina 10

- 5 - Updated: 8/17/12 Tech Note 4. Verify polling loop voltage on the control panel and at the RPM. a. This should be fluctuating betwe

Pagina 11

- 6 - Updated: 8/17/12 Tech Note V-plex Smoke Detectors 1. Check troubleshooting section under “Random Checks” regarding dip/serial modes a

Pagina 12

- 7 - Updated: 8/17/12 Tech Note Check 97/997 (polling loop short) Indicates that there is a physical short or Low Voltage on the polling lo

Pagina 13

- 8 - Updated: 8/17/12 Tech Note Total Load (ma @ 11.5) Vdc 22 ga 20 ga 18 ga 16 ga 1-16 6,000 6,000 6,000 6,000 17-24 4,850 6,000 6,00

Pagina 14

- 9 - Updated: 8/17/12 Tech Note Using the 4297 Polling Loop Extender Module (applies to panels with 128ma on polling loop) The 4297 V-plex