VISTA-50P/VISTA-50PUL Installation and Setup Guide
4-4
Zone Number Designations
The VISTA-50P/VISTA-50PUL supports up to 86 zones
of hardwire, polling loop and/or wireless protection,
distributed among up to 8 partitions. The following
table lists the zone numbers and the types of sensors
that can be used with each, and some alternate
functions of the zones.
Zone Function
1 2-wire Smoke Detectors (if used)
5 Audio Alarm Verification (if used)
7 Keyswitch (if used)
8 Latching-Type Glassbreak Detectors (if used)
1-9 Traditional Hardwired Zones
9 Selectable for fast response devices (if used)
1-86 5800 Series Wireless Devices
10-86 Polling Loop Devices
95
✳ + 1 Panic
96 # + 3 Panic
99
✳ + # Panic
Zone Defaults
Zone # Zone Type Zone # Zone Type
01 09 88 00
02 03 89 00
03 03 90 00
04 04 91 00
05 03 92* N/A
06 03 95 00
07 03 96 00
08 03 97 05
09 03 98 00
10–86 00 99 06
87 00
* Zone 992 is the Duress zone. Programming of the zone
response type is not applicable. This zone requires only the
report code programming.
Zone Index
The zones are designated as follows:
ZONE #
RANGE
ZONE
FUNCTION
ACTUAL ZONE
01 – 86 Protection
zones
As indicated
87, 88, 89,
90, 91, 97
& 98
System
Supervisory
Zones
87: VIP Module Supervision
88: 2
nd
Wireless Receiver –
not receiving signals
89: 2
nd
Wireless Receiver –
not talking to control
90: 1
st
Wireless Receiver –
not receiving signals
91: 1
st
Wireless Receiver –
not talking to control
97: Polling Loop (short
circuit)
98: Bell Supervision
92, 95 – 99 Duress and
Keypad Panics
92: Duress
95: 1 + ✳ panic (A key)
96: 3 + # panic (C key)
99: ✳ + # panic (B key)
Supervisory zones should be given a response type of 05
(Trouble by Day, Alarm by Night).
Communication Defaults
*45 PRIMARY FORMAT [1] ADEMCO Contact ID
*46 LOW SPEED FORMAT (Prim) [0] ADEMCO Low Speed
*47 SECONDARY FORMAT [1]
ADEMCO Contact ID
*48 LOW SPEED FORMAT (Sec.) [0]
ADEMCO Low Speed
*49 CHECKSUM VERIFICATION [0] [0]
No checksum Primary Secondary
*50 SESCOA/RADIONICS SEL. [0] Radionics
*51 DUAL REPORTING [0]
no
*52 STANDARD/EXPANDED REPORT FOR PRIMARY
[0] [0] [0] [0] [0] [0]
standard
Alarm Rstr Bypass Trbl Opn/Cls Low Bat
*53 STANDARD/EXPANDED REPORT FOR SECONDARY
[0] [0] [0] [0] [0] [0]
standard
Alarm Rstr Bypass Trbl Opn/Cls Low Bat