VISTA-50P/VISTA-50PUL Installation and Setup Guide
3-20
Long Range Radio Connected to the J7 Triggers
These triggers may be used to trip auxiliary alarm
signaling equipment such as the 7720, 7720ULF, and
7920SE Long Range Radios.
The triggers are common to all partitions and must be
enabled for each partition (field 2✳20).
The fire and burglary/audible panic alarm triggers are
normally LOW and go HIGH until a User Code + OFF
is entered in all enabled partition(s) that display these
conditions.
The silent panic/duress trigger latches HIGH, except for
duress, which is momentary.
Refer to the installation instructions that accompany
your radio for the connections to the control panel.
Installing a 4100SM
The 4100SM is used to print event log reports to a
serial printer.
NOTE: See SECTION 4: Programming for the
programming details when using the 4100SM.
Serial Printer Configurations
Configure the serial printer as follows:
• 8 data bits, no parity, 1 stop bit
• 300 or 1200 baud
Connecting the 4100SM to a Serial Printer
To connect a serial printer using the 4100SM, refer to
Figure 3-25 and perform the following steps:
Step
Action
1
Connect terminal 1 on the 4100SM to the
Violet wire on the 4142TR cable.
2
Connect terminal 6 on the 4100SM to the
Brown wire on the 4142TR cable.
3
Connect the 4142TR cable to J8 on the
control.
4
Connect terminals 8 and 7 of the 4100SM to
terminals 6 and 7 (aux. power (+) and (-)),
respectively of the control.
5
Connect the UL EDP Listed serial printer to
the 4100SM Interface Module.
The 4100SM Module is supplied with a 10-
foot RS232 cable. A longer cable can be used
if the VISTA-50P/VISTA-50PUL is separated
from the serial printer by more than 10 feet,
but the total cable length should be less than
50 feet.
123456789
NU
J8 CONNECTOR
VIOLET
GREY
YELLOW
RED
GREEN
BROWN
BLUE
BLACK
IN 2
IN 3
GROUND
OUT 5
OUT 6
GROUND
GROUND
PRINTER DTR
4142TR CABLE (SUPPLIED WITH 4100SM)
8
7
6
5
4
3
2
1
4100SM SERIAL MODULE
+ PWR
- (GND)
RXD
not used
not used
TXD
not used
DTR
BLUE WHITE
To TB6 Aux. Power (+)
(25mA current draw)
To TB7 Aux. Power (-)
USE GENDER CHANGER
SUPPLIED WITH 4100SM
IF PRINTER HAS DB25
MALE CONNECTOR
3M
Cable
Supplied with
4100SM
SERIAL PRINTER
SET FOR: 8 DATA BITS
EVEN PARITY
STOP BIT
300/1200 BAUD
4100SM JUMPERS
(CUT TO SET RESPECTIVE SIGNAL FLOATING)
COLOR FUNCTION PIN #
RED
BLUE
WHITE
CD
CTS
DSR
8
5
6
RED
4100SM-011-V0
Figure 3-25: 4100SM Using a Serial Printer
NOTE: See the 4100SM Installation Instructions for
details concerning the serial printer operation.
Installing the 4285/4286 VIP Module
The 4285/4286 VIP Module is an add-on accessory that
permits the user to access the security system (and
relays) via a TouchTone telephone. This may be done
either from the premises or by calling the premises from
a remote location. Only one VIP Module can be used in
a security system. This module must be enabled as
Device Address 4 in the Device Programming in #93
Menu Mode, and must be assigned to a partition.
U
L
The 4285/4286 VIP Module is not permitted in
UL installations.
Detailed operating instructions for phone access
to the security system are provided with the VIP
Module.