xiii
Program feature or option
Permitted in
UL864? Y/N
Possible settings Settings permitted in UL 864
3
50 ZONE TYPE
RESTORE ENABLES
FOR TYPES 16-18
N 0 = disable
1 = enable
Must be set to “1” (enable).
3
59 ENABLE BELL 2 &
AUXILIARY RELAY
CHIME ANNUNCIATION
N 0 = disable
1 = enable
Must be set to “0” (disable) if
Bell 2 or Aux Relay is used
for Fire.
3
60 BELL 2 & AUX
RELAY TIMEOUT
Y Enter 01-15 multiplied by 2
minutes.
00 = no timeout.
Must be set to “3” (Minimum
of 6 minutes).
3
82 BURGLARY
FEATURES ON
PARTITION 1 ENABLE
N 0 = disable
1 = enable
Must be set to “0” (disable).
RESTRICTION FOR FIRE
RELAYS
Y
Yes
No
Restriction for # 70 must be
set to Yes when
programming fire relays.