Connect the positive (+) phone wire to the ‘+/T” teminal and the
negative (-) phone tire to the “-/R” ter~nd.
When all the phone lines have been connected, they may he tested at
anY time bY m~entarily pressing the SYSTEM TEST button on the
No. 685’s front panel.
Within 10 seconds, all of the phone lines will
be tested. If SOY of the lines shows a f~lme, check the polarity of
the tiri~.
fiso check to tie sme that the phone ltie has been
connected to the line card tia the 3 pin connector located at the top
of the ltie -d.
~ aut-tic test of the telephone lines till be made by the NO. 685,
if no calls are received for 10 minutes. The test occurs as follows:
1) The Dhone line is seized for 2 seconds.
2) A check is made for loop current in the line. If no current is
found, a phone line failure will be flagged and a message will be
generated.
3)
The line is returned to the “On hookn condition.
Regular maintenance and
frequent testing by the
~y alarm systm.
TO TSR ~STALLSR
inspection (at least annuslly) by the installer and
user are vital to continuous satisfactory operation of
The installer shotid assume the responsibility of developing and offering
a
regular
maintenance prosram to the user as well as acquainting the user with the
proper operation and limitations of the alarm system and its component parts.
Recommendations must be included for a specific program of frequent testing (at
least weekly) to iname the system!s proper o~ration at all times.
I
.
AC POWSR LIGHT OFF
I
A.
AC ~wer loss. Operating on battery.
. SYSTEM OPERAT~G
B.
Fuse Blmn (3A SLO-BLO, e g., No. ~-10).
AC POWSR LIGHT OFF A. AC rower 10SS. ~ttery
. SYSTEM NOT OPERATING Dead or Disconnected.
B. Check fuses.
. AC POWER LIGHT ON A. Depress SYSTRM RESET swit~.
SYSTSM NOT OPERATING
B.
Remove power (AC and battery)
(NOT ANSWR~NG ALAR~)
and reset all cards.
LHE FAULT DISPLAYED A.
Check phone
line connections.
FOR L~ES #1 B. Check phone line voltaga and Wlsrity (see
THROUGH 8. Section VIII B).