DIALER PROGRAMMING (
40
52)
In fields
40,
41,
42, enter up to the number of digits shown. Do not fill unused spaces. Enter 09; # +11 for
; # +12 for
#; # +13 for a 2-second pause.
40
PABX ACCESS CODE
| | | | |
Enter 6 digits. If fewer than 6 digits are entered, exit
by pressing
(and press 41, if entering next field).
To clear entries from field, press
40
.
41
PRIMARY PHONE NO.
Enter up to 20 digits; do not fill unused spaces. If
fewer than 20 digits entered, exit by pressing
(and
press 42, if entering next field). To clear entries from
field, press
41
.
42
SECONDARY PHONE NO.
Enter up to 20 digits; Do not fill unused spaces. If
fewer than 20 digits entered, exit by pressing
(and
press 43, if entering next field). To clear entries from
field, press
42
.
43
PRIMARY SUBSCRIBER ACCOUNT NUMBER
| | |
[15 15 15 15]
44
SECONDARY SUBCRIBER ACCOUNT NUMBER
| | |
For fields
43 and
44:
Enter 09; # +11 for B; # +12 for C; # +13 for D;
# +14 for E; # +15 for F. Enter
as 4th digit, if 3+1
dialer reporting is to be used. If only 3 digits used,
exit by pressing
(and press next field).
To clear entries from field, press
43
or
44
.
Examples:
For Acct.
1234
, enter: 1 | 2 | 3 | 4
For Acct.
B234
, enter: #+11| 2 | 3 | 4
45
PHONE SYSTEM SELECT [1]
If Cent. Sta.
IS NOT
on a WATS line: 0 = Pulse Dial;
1 = Tone Dial; if Cent. Sta.
IS
on
a WATS line: 2 = Pulse
Dial ; 3 = Tone Dial.
46
REPORT FORMAT [7]
[7]
Primary Secondary
0
= 3+1, 4+1 ADEMCO L/S STANDARD
1
= 3+1, 4+1 RADIONICS STANDARD
2
= 4+2 ADEMCO L/S STANDARD
3
= 4+2 RADIONICS STANDARD
6
or undefined
= 4+2 ADEMCO EXPRESS
7
= ADEMCO CONTACT ID REPORTING
8
= 3+1, 4+1 ADEMCO L/S EXPANDED
9
= 3+1, 4+1 RADIONICS EXPANDED
47
SPLIT/DUAL REPORTING [0]
0 = Disable (Backup report only)
TO PRIMARY PHONE No.
TO SECONDARY PHONE No.
1 = Alarms, Restore, Cancel Others
2 = All except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel All
4 = All except Open/Close, Test All
5 = All All
TO PRIMARY PHONE No.
TO PAGING No. * (Secondary)
6 = All except Open/Close Alarms, Open/Close, for users
5-25*, Troubles
7 = All reports Alarms, Troubles
8 = All reports Alarms, Open/Close, for users
5-25*, Troubles
9 = All except Open/Close Open/Clos e fo r use rs
5-25*
*
Will report users 5-16 and, if using wireless button-type
devices, will report the zone number of the arm or disarm
button (10-25). Open/Close for users 1-4 are not reported.
**
See Installation Instructions for an explanation of the paging
format.
48
DIALER DLY (BURG/FIRE) (in sec) [10]
|
0 = no; 1 = 15; 2 = 30; 3 = 45; 4 = 60;
Burg/Fire
5 = 120. 0 for UL installations.
49
PERIODIC TEST REPORT [0]
0 = none; 1 = 24 hours; 2 = weekly; 3 = 30 days
(Enter Test Code in field
64.)
50
TEST REPORT OFFSET [2]
51
SESCOA/RADIONICS SELECT [0]
0 = Radionics (0 9, B F reporting); 1 = SESCOA
(0 9 only reporting). Select 0 for all other formats.
52
CANCEL VERIFY [1]
0 = no; 1 = yes
Entry of a number other than the one specified will give unpredictable results.