2
1234 567 89
J2 CONNECTOR
BLACK
GREY
YELLOW
RED
GREEN
BROWN
BLUE
VIOLET
4142TR CABLE (SUPPLIED WITH 4100SM)
4100SM
SERIAL
MODULE
+ PWR
- (GND)
RXD
NOT USED
NOT USED
TXD
NOT USED
DTR
BLUE WHITE
TO
AUTOMATION
EQUIPMENT
(RS232 INTERFACE)
RED
4100SM-015-V1
AUX PWR.
AUX GND.
11 12
CONTROL PANEL
WHITE
8
7
6
5
4
3
2
1
Figure 2: Wiring the 4100SM for Home/Facility Automation Control
Important Notes:
• For information regarding Crestron equipment and software required for interfacing to the control
panel, contact Crestron at 1-888-CRESTRON (273-7876).
• For information regarding AMX equipment and software required for interfacing to the control panel,
contact their support services.
• The outputs of the ADEMCO VA8201 Module and the ADEMCO 4100SM are serial (RS232) outputs.
• The distance between the ADEMCO VA8201 or the ADEMCO 4100SM and the Control Panel
cannot be further than the length of the 4142TR Trigger Cable.
• The distance between the ADEMCO VA8201 or the ADEMCO 4100SM and the 3rd party
Home/Facility Automation hardware can be up to 50’. If shielded wire, wire in conduit, or Cat 5
unshielded is used, the maximum distance is 25’.
Programming the Control Panel for Home/Facility Automation Control
For detailed information concerning the control panel’s programming procedures, refer to the control panel’s
Programming Guide.
Programming for the ADEMCO VA8201
✳05 Enter 1 to view all zone faults/restores;
enter 0 to view only events enabled in field
1✳79
✳14 Enter 1 for Home/Facility Automation
Control (cannot use both a serial printer
and Home/Facility Automation)
1✳78 Extended Home Control Event Reports
(1=extended; 0=limited)
1✳79 Home Control Event Report Types
(1=enable; 0=disable)
2✳30 Enter 1 to enable the VA8201
3✳19 Enter 1 for Home/Facility Automation
Control
NOTE: Fields ✳14, 2✳30 and 3✳19 MUST be set
for Home/Facility Automation Control.
Programming for the ADEMCO 4100SM
✳05 Enter 1 to view all zone faults/restores;
enter 0 to view only events enabled in field
1✳70
✳14 Enter 1 for Home/Facility Automation
Control (cannot use both serial printer and
Home/Facility Automation)
1✳78 Extended Home Control Event Reports
(1=extended; 0=limited)
1✳79 Home Control Event Report Types
(1=enable; 0=disable)
2✳30 Must be set with a 0
3✳19 Enter 1 for Home/Facility Automation
Control
NOTE: Fields ✳14, and 3✳19 MUST be set for
Home/Facility Automation Control.