An ADEMCO Group Company
ADDITIONAL FEATURES
Notification Appliance Circuits (Two)
— Programmable
— Temporal code compliant
— Individually silenceable
Programmable on-board auxiliary relay
SIA false alarm reduction features:
— Exit error logic
— Exit delay reset
— Cross zoning
— Call waiting defeat
— Recent close report
Supports hardwired, V-Plex (addressable) polling
loop and wireless zones
Hardwired zones
— Provides eight style B hardwired zones
— EOLR supervised for Fire and UL burglary
installations
— Supports N.O or N.C. sensors
— Individually assignable to one or all eight
partitions
— Up to 16 two-wire smoke detectors on zones
one and two (32 total)
— Four-wire smoke or heat detectors on zones
one to eight
— Up to 50 two-wire glass break detectors on
zone eight
Patented V-Plex (addressable) polling loop
technology
— Supports up to 120 two-wire multiplex
zones/points
— Can use existing wiring
— Global polling technology for faster
processing
— Increased current draw capacity (128mA)
— Individually assignable to partitions,
notification circuit (bell) output or aux relay
— 4,000 ft capability without the use of
shielded cable
— Extender/Isolation bus module
— Two-wire smoke detector zone/group
expansion module adds two or four zones
— Eight zone - Class A and B extender module
— Eight zone - Class B extender module
— One zone supervised contact monitor module
UL Listed wireless smoke detector expansion
— Supports up to 87 wireless zones using 5881
receiver
— Supervised by control for check-in signals
— Tamper protection for transmitters
— Individually assignable up to eight partitions
— Supports UL864/NFPA listed/complaint
wireless smoke detectors
Scheduled uploading of events to central station
VISTA-100
control/communicator
12345678
ARMED
READY
ARMED
READY
Commercial
Wireless
Devices
Key switch
option
4-146
5140 LED Communicator
Status Module
5140DLM
8 CLASS B HARDWIRE ZONES
4100SM
Printer
Interface Module
RS232
6220S Printer
Phone line to Control Station
772OULF
Long Range Radio
Transmitter
-5881 Series
Wireless Receiver
(Max two)
V-Plex Loop
-32 Character
Red- Alpha
Keypad
-Programmable
Relay
-Supervised Relay
or NAC (Bell) circuit
Additional Notification Circuits
using 4204 CF Module
4208U
4193SN
4193SN
5881 RF Receiver
5881 RF Receiver
Glass break Detectors
Manual Pull Stations
MPS - 1*
MPS - 2*
MPS - 5*
MPS - 10*
Tamper Switch*
Flow Switch*
Low Temp Switch*
*Use w/4193SN
Mini-Zone Module
4208U 8 Contact
Zone Module
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
2-ZN Module
4209U Group
Zoning Remote
Module
4209U 4208SNF
APPLICATIONS
The VISTA-100 control is well suited for a variety of applications as
an integrated fire and burglary control. A diverse line of ADEMCO
initiating and control devices supports this extremely powerful
control. Some of the applications supported are: medical and
professional buildings, supermarkets, churches or synagogues, office
buildings, schools, universities, strip malls, and factory or warehouse
environments.
INSTALLATION
The VISTA-100 alarm system has been designed to mount both
quickly and easily in an attack resistant cabinet. It meets all
applicable requirements for UL commercial Fire and Burglary
installations and is NFPA72 compliant.
SPECIFICATIONS
Electrical:
Primary power:
— 120VAC to ADEMCO No. 1451 Transformer Secondary rated
18VAC, 72VA
Quiescent current draw:
— 350mA
Backup battery:
— 12VDC, 12AH min to 34.4AH max
— Lead acid battery (gel type)
Alarm power:
— 12VDC, 1.7A max for each notification (bell) circuit output
Backup battery:
— 12VDC, 12AH min to 34.4AH max
— Lead acid battery (gel type)
Alarm power:
— 12VDC, 1.7A max for each notification (bell) circuit output
Aux. standby pwr:
— 12VDC, 1A max
Total power:
— 2.3A at 12VDC, 3.4A at 24VDC from all sources
Standby time:
— 24 hours with 1A standby load or 60 hours with 205mA max
standby load using 34.4AH battery
Fusing:
— Battery input, aux. and notification (bell) circuit outputs are
protected using PTC circuit protectors. All outputs are power
limited.
Main Dialer:
Line seize:
— Double Pole
Ringer equiv.:
— 0.7B
Formats:
— ADEMCO Low Speed, ADEMCO 4+2 Express, ADEMCO High
Speed, ADEMCO Contact ID, Sescoa and Radionics
4297
VISTA-100
Notification (Bell) Circuits
5192 Series Smoke Detectors
4192 Series Smoke Detectors
5881EH